Product image is representative; revision or series may vary. Contact us to request a specific version.
The Allen Bradley 152H-WBC-50 solid-state controller is designed for robust motor control applications. Rated for 600 V AC, this controller operates at frequencies of 50/60 Hz and manages 3-phase motors up to 100 HP efficiently.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Allen Bradley |
|---|---|
| Product Type | Solid-state controller |
| Product Line | SMC Plus |
| Part Number | 152H-WBC-50 |
| Weight | 100.00 lbs (45.36 kg) |
| Enclosure Type | NEMA 1 ventilated |
| Rated Voltage | 600 V AC |
| Frequency Rating | 50/60 Hz |
| Phase Type | 3 phase |
| Motor Rating | 100 HP |
| Rated Current | 115 A |
| Start Methods | Soft start, current limit, full voltage |
| Initial Torque | 5–90% LRT |
| Acceleration Time | 2–30 s |
| Kickstart | Selectable boost |
| Kickstart Current | 550% FLA |
| Kickstart Time | 0.4–2 s |
| Current Limit | 50–500% FLA |
The 152H-WBC-50, a solid-state controller from Allen Bradley's SMC Plus series, caters to high-performance motor management. Supporting a rated voltage of 600 V AC, it functions effectively within typical industrial frequency standards of 50/60 Hz. This controller is developed for use with 3-phase motors, providing a motor rating capacity of up to 100 HP. Additionally, it has a rated current of 115 A, ensuring reliability in demanding conditions. The 152H-WBC-50 facilitates multiple start methods, including soft start, current limit control, and full voltage start options, which enhance operational flexibility based on application needs.
For initial startup torque, this model is capable of adjusting between 5% and 90% of LRT, allowing operators to tailor performance to specific applications. It features an adjustable acceleration time that can be set between 2 and 30 seconds, which can be fine-tuned to transition motors smoothly without sudden load changes.
Furthermore, the selectable kickstart feature provides an initial surge of 550% FLA, ensuring that the motor easily overcomes inertia during startup or under heavy load conditions. The kickstart duration can be set from 0.4 seconds to 2 seconds, allowing for precise control during the starting phase. Lastly, the current limit can be configured between 50% and 500% of FLA, providing essential overload protection and adaptability to varying load requirements. Overall, the 152H-WBC-50 solid-state controller is engineered for optimized performance, ensuring reliability and efficiency in a variety of motor control applications.
| Revision Part # | Also known as | |
|---|---|---|
| 152H-WBC-50 Ser A | 152H-WBC-50/A, Series A, Rev A | |
| Don't see your particular revision? Contact us now. | ||