The 153H-WAC-44 is a solid-state motor controller, featuring an integrated circuit breaker designed for reliable motor startup functionality. Catered for applications with a rated voltage of 600 volts AC, this unit manages motors rated up to 25 horsepower, making it suitable for various industrial needs.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Allen Bradley |
|---|---|
| Product Type | Solid-state motor controller with circuit breaker |
| Product Line | SMC Plus |
| Part Number | 153H-WAC-44 |
| Weight | 100.00 lbs (45.36 kg) |
| Soft Start Method | Voltage ramp starting |
| Initial Torque Range | 5–90% locked rotor torque |
| Acceleration Time | 2–30 s adjustable |
| Enclosure Type | NEMA Type 1, IP30 |
| Rated Voltage | 600V AC |
| Frequency | 50/60 Hz |
| Motor Rating | 25 HP |
| Rated Current | 28 A |
| Control Supply | 120V AC control power |
| Overload Protection | 3-pole thermal overload relay |
| Soft Stop Time | 2–60 s adjustable |
| Current Limit Range | 50–500% full load current |
| Kickstart Duration | 0.4–2 s adjustable |
| Kickstart Level | 550% full load current |
The 153H-WAC-44 solid-state motor controller by Allen Bradley offers a comprehensive approach to motor management and protection. This device operates with a nominal voltage of 600V AC and is suitable for both 50 and 60 Hz applications. Capable of handling motors rated up to 25 horsepower, it delivers a robust performance tailored for industrial environments.
This controller utilizes voltage ramp starting as its soft start method, which aids in reducing mechanical shock during startup. Additionally, the initial torque can be set between 5% and 90% of locked rotor torque, allowing for flexibility in motor engagement based on application requirements. Users can adjust the acceleration time from 2 seconds to 30 seconds, supporting various process demands during motor startup.
Furthermore, the controller's soft stop feature ensures a smooth motor shutdown, adjustable between 2 to 60 seconds. Combining effective performance with safety, it includes a 3-pole thermal overload relay that protects the motor from overheating.
Current limiting functions are also a feature, with a range of 50% to 500% of full load current, allowing the drive to handle sudden load changes gracefully. When needed, a kickstart can be applied, lasting from 0.4 seconds to 2 seconds, with a level set at 550% of full load current to assist with initial movement when necessary.
The NEMA Type 1 enclosure provides adequate protection for indoor applications, rated at IP30, ensuring the controller's reliability in controlled industrial settings. Additionally, the controller requires a 120V AC control power supply for operation, further simplifying its integration into existing systems.