Product image is representative; revision or series may vary. Contact us to request a specific version.
The 1410-EOB50 is a Motor Winding Heater from Allen-Bradley. This device is used with AC motors to prevent condensation built-up on motor winding, preventing damage. This device is rated 460 VAC, 3-Phase at a frequency of 60 Hz. It is applicable with a motor horsepower range of 24 - 100 HP.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Allen Bradley |
|---|---|
| Product type | Motor winding heater |
| Product Line | 1410 Motor Protection |
| Part Number | 1410-EOB50 |
| UPC | 662072117613 |
| Weight | 1.88 lbs (0.85 kg) |
| Series | Bulletin 1410 |
| Product Description | Motor Winding Heater |
| Voltage rating | 460 Volts AC |
| Motor Voltage | 460 VAC, + 10%, -15% |
| Frequency rating | 60 Hertz |
| Input phase | 3-Phase |
| Horsepower | 25 to 100 Horsepower |
| Input frequency | 60 Hz |
| Operating temperature | 32 to 122 degrees Fahrenheit |
| Motor Horsepower Range | 24-100 HP |
| Storage temperature | -13 and 184 degrees Fahrenheit |
| Fuse Protection | 200,000 A |
| Transient Voltage protection | Metal Oxide Varistor |
| Power to motor | 3 Watts / Horsepower |
| Rate of change limiter | RC Snubber Circuit |
| Design standard | NEMA ICS - 1970; NEC; UL; CSA |
| Mounting Holes | 7/32 inch or 5.6 mm diameter |
| Product Lifecycle | Discontinued |
The 1410-EOB50 is an Allen-Bradley manufactured AC Motor protection device. The part number refers to a Motor Winding Heater, used to prevent a build-up of condensation, preventing damage to the motor winding. This heater is designed for installation to an AC motor with a Horsepower range of 24-100 HP and motor voltage of 460 VAC, + 10%, -15%, 3-Phase, 60 Hz. The 1410-EOB50 Motor Winding Heater has an operating temperature of 0 to 50 Degree Celsius while the storage temperature is -25 to 85 Degree Celsius. The motor heater is intended to be wired to the contacts of a motor starter that will energize the heater when the starter has started. Conversely, the heater must be de-energized when the motor starter is shut down. Furthermore, with the heater energized, a Silicon Controlled Rectifier (SCR) shall be connected to the two terminals of the motor. The output voltage of the SCR shall hold the winding temperature at 5-10 Degrees above the ambient temperature. Protection circuits such as Metal Oxide Varistor (MOV) or Resistor - Capacitor (RC) snubber circuit can be installed to protect the device from transient voltage and limit voltage rate of change. The 1410-EOB50 heater has physical dimensions of 4.5 inches or 114.3 mm (H) x 3.5 inches or 88.9 mm (D) x 5 ¾ or 146.1 mm (L). The heater can be mounted in any orientation however, the printed circuit board must be facing up. Four mounting holes are provided with the heater measuring 7/32 inch or 5.6 mm diameter. It is required to install this motor winding heater when the motor is disconnected from the power source.
The Allen-Bradley 1410-EOB50 heater is a solid-state motor winding heater. Adjustments are not required on the 1410-EOB50 heater to make it work. It belongs to the Bulletin 1410 series of motor protection devices. The 1410-EOB50 heater is designed for use with three-phase AC motors to protect them against the damage which is caused by the build-up of condensation on motor windings in environments with high levels of humidity. The 1410-EOB50 heater should not be used to dry wet/damp motors. The 1410-EOB50 heater can be used with three-phase AC squirrel-cage motors which are controlled by automatic full-voltage starters. The ambient operating temperature range for the 1410-EOB50 heater is 32 to 122 degrees Fahrenheit. Unused 1410-EOB50 heaters should be kept in environments where the ambient temperature is between -13 and 184 degrees Fahrenheit. The approximate power delivered to the motor by the 1410-EOB50 heater is 3 Watts. The 1410-EOB50 heater can be used with motors rated for 25 to 100 Horsepower of output. The voltage rating for the 1410-EOB50 heater is 460 Volts AC. The line frequency rating is 60 Hertz. The 1410-EOB50 heater applies voltage to the motor winding. This winding voltage varies by ±5% for the line voltage variations of +10% to -15%. A metal oxide varistor on the 1410-EOB50 heater protects motors against voltage surges. An RC snubber circuit is also provided to limit the rate of the change of voltages on the circuit. The 1410-EOB50 heater is certified by the CSA and UL standards and it is approved by the CSA and UL 508 standards. The true RMS output current is 15% of the full load current. The dimensions of the 1410-EOB50 heater are 114.3 x 146.1 x 88.9 millimeters.
Yes, the 1410-EOB50 includes a free 2-year DO Supply warranty. You can upgrade to a 3-year warranty at checkout for even more protection.
The voltage rating of the 1410-EOB50 is 460 VAC, + 10%, -15%, 3-Phase, 60 Hz.
The 1410-EOB50 is installed to a motor rated 24 - 100 HP.
The 1410-EOB50 Supports any mounting orientation. Only the circuit board must be facing up.
The Allen-Bradley 1410-EOB50 heater is a solid-state motor winding heater. User adjustments are not required on the 1410-EOB50 heater. It belongs to the Bulletin 1410 series of motor protection devices. The 1410-EOB50 heater is designed for use with 3-phase AC motors to protect it against damage which is caused by the build-up of condensation on motor windings in environments with high levels of humidity.