Product image is representative; revision or series may vary. Contact us to request a specific version.
The 190-P060 from Allen Bradley operates as a thermal-magnetic trip block, engineered to adjust within a thermal range of 4 to 6 Amperes. It is capable of accommodating a magnetic range adjustable from 50 to 80 Amperes, suitable for diverse applications that require reliability and efficiency.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Allen Bradley |
|---|---|
| Product Type | Thermal-magnetic trip block |
| Product Line | 190 Starters |
| Part Number | 190-P060 |
| Weight | 0.56 lbs (0.26 kg) |
| Thermal Range | 4–6 A adjustable |
| Magnetic Range | 50–80 A adjustable |
| Short-trip Multiplier | ~8.5–14 × thermal setpoint |
| Thermal Accuracy | ±5 % @ 40 °C; ±10 % @ 60 °C |
| Magnetic Tolerance | ±20 % |
| Rated Insulation Voltage | 690 V AC |
| Continuous Current | 42 A |
| Frequency | 50–60 Hz |
| Power Loss | 14–23 W (typical) |
| Short-circuit Capacity | Up to 3–4.5 kA @ 690 V |
| Making / Breaking | ≈ 400 A AC |
| Phase-loss Response | Phase-sensitive |
| Terminal Capacity | 1–16 mm² (single) |
| Mounting Position | Any, ±30° vertical |
The Allen Bradley 190-P060 is designed as a thermal-magnetic trip block, focusing on functionality and adaptability. It features a thermal range that can be finely adjusted from 4 A to 6 A, along with a magnetic range that accommodates settings between 50 A and 80 A.
In terms of performance metrics, this equipment includes a short-trip multiplier that is approximately eight-and-a-half to fourteen times the specified thermal setpoint. Thermal accuracy is well within ±5 % at temperatures around 40 °C, while it is ±10 % at elevated temperatures up to 60 °C. Coupled with a magnetic tolerance of ±20 %, this ensures reliable operation in varying conditions.
The trip block supports a continuous current handling capability of 42 A, making it suitable for demanding applications. Power loss typically lies between 14 and 23 W, reflective of its efficient design. The unit complies with 50 to 60 Hz frequency ratings and has a rated insulation voltage of 690 V AC. For short-circuit scenarios, it can handle capacities up to 3–4.5 kA, ensuring protection in high fault conditions.
The making or breaking capacity is noted at approximately 400 A AC. It also has a phase-sensitive response to phase loss, enhancing operational safety. Terminal connections can accommodate wire sizes ranging from 1 mm² to 16 mm² for single-term connections. The mounting orientation offers flexibility, permitting installation in any position within a ±30° vertical range.