The 592-EC5PC is an electronic overload relay from Allen-Bradley’s E3 Plus series. This is a protective electrical device that comes with Voltage monitoring capability, a current trip adjustment rating of 0.4-2.0 Amperes, NEMA operating voltage of 600 V, and IEC operating voltage of 690 / 1000 V. It has a microprocessor type overload sensing capability with an adjustable trip class of 5-30. This overload relay is also capable of detecting Overcurrent (Jam) Detection, stall detection, underload detection, and current imbalance. It comes with a manual/automatic reset.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Allen Bradley |
|---|---|
| Product Type | Overload Relay |
| Product Line | 592 Overload Relays |
| Part Number | 592-EC5PC |
| UPC | 612598752133 |
| Weight | 0.81 lbs (0.37 kg) |
| Product Family | Electronic Overload Relay |
| Product Category | E3 Plus with Voltage monitoring |
| Relay Type | Solid-State |
| Current Adjustment range | 0.4-2.0 Amperes |
| Overload Relay Type | 592-EC5 |
| NEMA Operating Voltage | 600 V |
| IEC Operating voltage | 600 V / 1000 V |
| Overload Type | Microprocessor |
| Full Load Current Range | 0.4 to 2.0 A |
| Reset type | Automatic and Manual reset |
| Compatible Devices | Bulletin 500 Contactors |
| Adjustment range | 5:01 |
| Supported Contactor Size | 0 to 2 |
| Phase loss | Adjustable delay |
| Compliance | IEC, CCC, CSA, UL, CE, ABS, C-tick, cULus |
| Overcurrent (Jam) Detection | Supported |
| Stall detection | Supported |
| Underload detection | Supported |
| Current imbalance | Supported |
| Discrete Inputs | Six (6) |
| Discrete outputs | Two (2) |
| PTC Thermistor monitoring | None |
The 592-EC5PC is a microprocessor-based electronic overload relay from Allen-Bradley. This is part of the E3 Plus series with integrated voltage monitoring capability as well as Overcurrent (Jam) Detection, stall detection, underload detection, and current imbalance. This overload relay has an adjustable current trip setting of 0.4 - 2.0 Amperes with a nominal voltage rating of 600V for NEMA and 690V / 1000V IEC operating voltage standards. The 592-EC5PC comes with a programmable memory that can be downloaded with simple logic routines composed of basic Boolean operands such as AND, OR, XOR, and NOT (Invert) as well as Timers, Counters, and output latches. These same operands may also be used to trigger outputs channels provided to this module to implement logic sequencing or interlocking function. This logic is downloaded via the DeviceLogix communication capability of the 592-EC5PC utilizing RSNetWorx for DeviceNet version 3.0 or later. The 592-EC5PC comes with embedded status indicators such as Network Status via the bi-color Green / Red indicator; Trip/Warn which is a bi-color Amber / Red color for depicting module warning and tripped status; Out A & B amber LED that energizes when contact outputs are commanded to close; IN 1-6 amber LED that illuminates when external input device delivers input signal. The 592-EC5PC has an operating temperature of -20…+55 °C (-4…+131 °F); Storage temperature of -40…+85 °C (-40…+185 °F); Operating vibration of 3G per IEC 68-2-6; Operating shock of 30G per IEC 68-2-27 standard and IP0 protection rating. This electronic overload has to phase current reporting accuracy of +/- 5% and +/- 10%, depending on the FLA setting.
The 592-EC5PC Overload Relay is manufactured by Allen-Bradley/Rockwell Automation as part of the 592 Overload Relay series and the E3 Plus Overload Relay product line with voltage protection and energy monitoring. It has a full load current range from 0.4 to 2 Amps. This relay is a solid-state relay and it is intended for use with the Bulletin 500 contactors with NEMA contactor sizes 0 to 2. The E3 Plus Overload Relay devices, including the Allen-Bradley 592-EC5PC Solid-State Overload Relay, are designed to allow the users to keep track of different diagnostics information such as the trip status, trip snapshot, hours of operation, number of starts, warning status, device status, overload trip time, and the history of the past five trips over the DeviceNet network. Other functions of these overload relays include allowing the operators to monitor operational data like the average current, individual phase currents, current imbalance percentage, ground-fault current, and the percentage of a thermal capacity that is utilized. When the RSNetWorx is used for version 3.0 or later versions of the DeviceNet network, the function block programs are configurable and they can be saved to the E3 Plus Overload Relays to help operate the single logic routines. The function blocks can be programmed through the use of standard Boolean operators such as XOR, AND, OR, and NOT and counters, latches, and timers are supported too. The Allen-Bradley 592-EC5PC Solid State Overload Relay features a remote trip function that helps external devices like vibration sensors to induce the E3 Plus Overload Relay to trip when necessary.
Yes, the 592-EC5PC includes a free 2-year DO Supply warranty. You can upgrade to a 3-year warranty at checkout for even more protection.
The 592-EC5PC has 0.4-2.0 Amperes current rating.
Yes. The 592-EC5PC is capable of DeviceLogix connectivity.
No. The 592-EC5PC is not provided with Thermistor or PTC input.
Allen-Bradley manufactures the 592-EC5PC Solid-State Overload Relay as part of the Bulletin 592 and E3 Plus Overload Relay series. It comes with a full load current range of 0.4 to 2 Amps. The contactor sizes that the relay supports are sizes 0 to 2.