Product image is representative; revision or series may vary. Contact us to request a specific version.
The 505-AOXD-23-101 from Allen Bradley is a NEMA full-voltage reversing starter suitable for various applications. This model operates at a voltage of 115-120 V AC, running on a 60 Hz supply, and is rated for continuous current up to 18 A.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Allen Bradley |
|---|---|
| Product Type | NEMA Full-Voltage Reversing Starter |
| Product Line | Bulletin 505 |
| Part Number | 505-AOXD-23-101 |
| Weight | 3.00 lbs (1.36 kg) |
| UPC | 662072202210 |
| Voltage | 115-120 V AC, 60 Hz |
| Size | NEMA Size 0 |
| Enclosure | Open Style |
| Continuous Current Rating | 18 A |
| Number of Poles | 3-pole starter |
| Overload Relay | None |
| Inrush Current | 140 A |
| Maximum Horsepower | 5 HP |
| Heat Dissipation | 5.9 W |
| Transformer Primary Switching kVA | 5.2 kVA |
| Temperature Range | –25°C to +65°C |
| Drop-Out Time (Average) | 14 ms |
| Operating (Pick-Up) Time | 22 ms |
The Allen Bradley 505-AOXD-23-101 is a full-voltage reversing starter characterized by its NEMA Size 0 design. This device functions efficiently at a voltage range of 115-120 V AC and is intended for a 60 Hz electrical system. The open-style enclosure allows for effective heat dissipation, rated at 5.9 W while facilitating easy access for maintenance.
Designed to operate without an overload relay, the starter is capable of delivering a continuous current rating of 18 A. Suitable for demanding applications, this unit supports up to 5 horsepower, accommodating a peak inrush current capacity of 140 A at startup.
The unit’s temperature operating range is rated between –25°C to +65°C, ensuring reliable performance in varied environments. The average drop-out time is effectively set at 14 ms, while the operational pick-up time measures at 22 ms, reflecting the starter's responsiveness. Furthermore, it is capable of switching a primary transformer capacity of 5.2 kVA, adapting well to a wide spectrum of load requirements.