The Allen-Bradley 140G-H6C3-C25 circuit breaker is a 3-pole circuit breaker from the Bulletin 140G product line. It comes with a molded case and it can be installed in an industrial cabinet for protection from dust, debris, and moisture. When it is installed in a cabinet, the 140G-H6C3-C25 circuit breaker supports an operating temperature range between 0 and 40 degrees Celsius or 32 and 104 degrees Fahrenheit. It supports a fixed thermal trip rating of 25 Amps and a fixed magnetic trip rating of 400 Amps. The 140G-H6C3-C25 circuit breaker can be used as the main line circuit protection device in a control panel or as a branch circuit protector.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more
Rockwell Disclaimer: The product is used surplus. DO Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because DO Supply is not an authorized distributor of this product, the Original Manufacturer's warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, DO Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. DO Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. DO Supply also makes no representations as to your right to install any such firmware on the product. DO Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Technical specifications for 140G-H6C3-C25

ManufacturerAllen Bradley
Product TypeMolded Case Circuit Breaker
Product Line140G MCB
Part Number140G-H6C3-C25
Weight3.38 lbs (1.53 kg)
FrameH
Amps125
Interrupting Rating65 kA
Protection TypeFixed Thermal/ Fixed Magnetic
Current Range25 A
Rated Insulation Voltage1000 V
Rated Impulse Withstand Voltage8 kV
Mechanical Life240 Operations/hr.
Electrical Life120 Operations/ hr.

The Allen-Bradley 140G-H6C3-C25 circuit breaker is an H Frame molded-case circuit breaker. It is rated for 25 Amps of current and it is part of 140G product line, which is available in 9 frame sizes with current ratings of up to 3000 Amps. The number of poles on the 140G-H6C3-C25 circuit breaker is 3and its weight is 2.65 pounds. The thermal/magnetic trip system on the breaker is fixed with a 400 Amps magnetic trip threshold and a 25 Amps thermal trip threshold. The dimensions of this H Frame circuit breaker are 82.5 x 90 x 130 millimeters (depth x width x height).  The rated mechanical life at 240 operations per hour is 25,000 hours. Allen-Bradley recommends the use of 75 degrees Celsius rated copper wire for circuit breaker terminations. The terminal lugs for the breaker need to be ordered separately.

The maximum recommended ambient working temperature for the 140G-H6C3-C25 circuit breaker is 40 degrees Celsius. At 120 operations per hour, the rated electrical life is 8000 hours. The 140G-H6C3-C25 circuit breaker complies with multiple international standards. For the IEC 60947-2 standard for DC voltages, the breaker is rated for 70 kiloamps of breaking capacity at 250 Volts DC and at 500 Volts DC. For the CSA 22.2 and UL 489 standards, the 140G-H6C3-C25 circuit breaker is rated for an interrupting capacity of 150, 65, and 25 kiloamps at 240, 480, and 600 Volts AC at 50 to 60 Hertz. A minimum of 8 AWG copper wire is recommended for the earthing of the 140G-H6C3-C25 circuit breaker. The presence of high voltages and currents could cause equipment damage and lead to injury. Therefore, prior to installation and maintenance, the main electrical power should be disconnected. Furthermore, harmful contaminants should not be allowed to come into contact with the circuit breaker.

Revision Part #Also known as
140G-H6C3-C25 Ser A140G-H6C3-C25/A, Series A, Rev A