Allen Bradley 140G MCB 140G-R12I3-E20

Product image is representative; revision or series may vary. Contact us to request a specific version.

140G-R12I3-E20

|

The Allen-Bradley 140G-R12I3-E20 Molded Case Circuit Breaker has a R Frame and 2500-3000 Amps. It also has a 125 kA Interrupting Rating and 3 Poles.

Call for an immediate quote
2 Year DO Supply Warranty
Available
Ships from Raleigh, NC
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more
Rockwell Disclaimer: The product is used surplus. DO Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because DO Supply is not an authorized distributor of this product, the Original Manufacturer's warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, DO Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. DO Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. DO Supply also makes no representations as to your right to install any such firmware on the product. DO Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Technical specifications for 140G-R12I3-E20

ManufacturerAllen Bradley
Product TypeMolded Case Circuit Breaker
Product Line140G MCB
Part Number140G-R12I3-E20
Weight32.00 lbs (14.51 kg)
FrameR
Amps2500-3000
Interrupting Rating125 kA
Protection TypeElectronic LSIG
Current Range2000 A
Rated Insulation Voltage1000V
Rated Impulse Withstand Voltage12 kV
Mechanical Life60 Operations/ hr.
Electrical Life60 Operations/ hr.

The 140G-R12I3-E20 3-pole molded case circuit breaker is an R-frame high-performance circuit breaker made by Allen-Bradley that is designed to provide circuits and connected equipment with protection from general overcurrents, short circuits, and thermal overcurrents. This R-frame circuit breaker can also serve as as the main disconnecting means for a control panel, and it comes with a high-precision electronic trip unit that allows for customization of protection curves for specific application needs. The 140G-R12I3-E20 circuit breaker has a rated short-circuit breaking capacity of 125 Kilo-Amps at 480 Volts 3-phase input (50/60 Hertz). It has a continuous current rating of 2000 Amps and a rated insulation voltage of 1000 Volts AC.

The 140G-R12I3-E20 circuit breaker has a life-time mechanical operation of 15000 at 60 operations per hour, and an electrical life-time of 60 operations per hour. This circuit breaker has an electronic type of trip unit with long, short, instantaneous, and ground fault trip ranges. It has a long trip range of 800 to 2000 Amps and a short trip range of 1200 to 20,000 Amps between 0.1 and 10 seconds of trip time. It also has a trip range of 3000 to 30000, and a ground fault trip range of 400 to 2000 Amps for 0.2 to 0.8 seconds duration. The 140G-R12I3-E20 circuit breaker, like all R Series circuit breakers, is designed for harsh and tough environmental conditions, and it supports a wide range of mounting orientations. It has an operating temperature limit of 40 degrees Celsius and can be stored at a temperature range of -40 to 80 degrees Celsius. The 140G-R12I3-E20 circuit breaker has total mounting dimensions of 427 x 282 x 382 millimeters and it weighs approximately 79.0 kilograms.

Revision Part #Also known as
140G-R12I3-E20 Ser A140G-R12I3-E20/A, Series A, Rev A
Don't see your particular revision? Contact us now.