Product image is representative; revision or series may vary. Contact us to request a specific version.
The Allen-Bradley 5069-OX4I is a Compact 5000 isolated relay output module. This module features Four (4) Form C, Normally Open (N.O.) / Normally Closed (N.C.) relay output channels that are individually isolated. This module operates at 5-125VDC and 5-264VAC. It has a switching frequency of 1 operation every 3 seconds (0.3 Hz at rated load). This module has output current of 2 A per channel and 8 A per module.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Allen Bradley |
|---|---|
| Category | PLCs |
| Product Line | CompactLogix 5069 |
| Part Number | 5069-OX4I |
| UPC | 885630530130 |
| Weight | 0.63 lbs (0.28 kg) |
| Output Voltage Range | 5-125VDC; 5-264VAC |
| Module Type | Relay output module |
| Series | Compact 5000 I/O |
| No. of Inputs | Four (4) individually isolated form C contacts |
| Relay Ratings | 2 A resistive per channel @ 5…30V DC; 2 Aresistive per channel @ 5…264V AC, 50/60 Hz; 2 A general use per channel @ 5…250V AC, 50/60 Hz and 2 A @ 5…125V AC, ATEX/IECEx. |
| Pilot duty rating | 5…240V AC, 50/60 Hz, C300 pilot duty per channel 5…125V DC, R150 pilot duty per channel |
| Output current per channel, max | 2:00 AM |
| Output current per module, max | 8:00 AM |
| Output Delay Time | 10 ms |
| Switching frequency | 1 operation every 3 seconds (0.3 Hz at rated load) |
| Initial contact resistance, max | 30 m? |
| Bounce time, mean | 500 µs |
| Fusing | Outputs are not fused |
| Expected contact life | 300K cycles resistive, 100K cycles inductive |
| Delay to Fault | Supported |
| Number of Inputs | N/A |
| Number of Outputs | 4 Form C (SPDT) |
| Voltage Category | N/A |
| Input Voltage Range | N/A |
| Power Dissipation | 2.6 Watts |
| Enclosure Type | None (Open Style) |
| CIP Sync Supported | Yes |
| Pattern Matching Supported | Yes |
The Allen-Bradley 5069-OX4I is a relay output module with Four (4) individually isolated Form C or Single Pole, Double Throw (SPDT) output channels. Both Normally Open (N.O.) and Normally Closed (N.C.) output contacts may be actively used externally to energize or actuate different loads. Each output channel of the 5069-OX4I has an output rating of 2 A per channel and 8 A per module. The output delay time of this module is typical for both signal transitions, exhibiting maximum delay time of 15 ms per channel. Additionally, contact outputs are expected to operate up to 300K cycles when connected to a resistive load and 100K cycles when wired to an inductive load.
The switching frequency of each channel is Once every Three (3) seconds or .3 Hz at rated load. Maximum initial contact resistance is 30 m? with bounce time of 500 µs.
The module has programmable output states in the event when the system enters fault state, fault and program mode. Available programmable states are Hold current state, Turn ON output and Turn OFF output with the latter being the default setting.
This module has MOD power rating of 75 mA @ 18…32V DC; maximum MOD Power Passthrough of 9.55 A @ 18…32V DC and maximum SA Power Passthrough of 9.95 A @ 0…32V DC. This module has maximum power dissipation 2.6 W and Thermal dissipation of 8.88 BTU/hr. Install this module to a DIN that is made with highly conductive, non-corrosive and oxidation resistant material. The DIN rail used with this devices connects the device to the grounding system.
The Allen-Bradley 5069-OX4I is supplied as open-type equipment. The 5069-OX4I is intended for industrial environments. This module can operate in an environment with a pollution degree no higher than Pollution 2 (as defined in EN / IEC0664-1) when the environment is a Zone 2 environment. The enclosure should be accessible only by means of the appliance. The relative humidity of this module is from 5 to 95% without condensation. The operating temperature of this module is 32 °F to 131 °F. The storage temperature of this module is -40 °F to 158 °F. The Allen-Bradley 5069-OX4I ha an operating shock of 15 g (3 pulses, 11 ms). The nonoperating shock of this module is 30 g (3 pulses, 11 ms). This module is designed to maintain optimum functionality at 2.5 g vibration.
| Revision Part # | Also known as | |
|---|---|---|
| 5069-OX4I Ser A | 5069-OX4I/A, Series A, Rev A | |
| Don't see your particular revision? Contact us now. | ||
Yes, the 5069-OX4I includes a free 2-year DO Supply warranty. You can upgrade to a 3-year warranty at checkout for even more protection.
The 5069-OX41 has Form C contact outputs.
Yes. Simultaneous connection may be present on both of the output contacts.
Yes. Different voltages may be used at each of the output channels.
The Allen-Bradley CompactLogix 5069-OX4I exhibits 4 Form C (SPDT), 2.6 Watts Power Dissipation, 5-264 Volts AC or 5-125 Volts DC, and an Open-Style Enclosure.