1756-L1

|

The 1756-L1 is a controller module for the ControlLogix Modular Programmable Automation Controller (PAC) by Allen-Bradley. It comes with Memory of 2MB, and built-in RS232 communication interface. It is capable of 128,000 Discrete I/O and 4000 Analog I/O memory.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more
Rockwell Disclaimer: The product is used surplus. DO Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because DO Supply is not an authorized distributor of this product, the Original Manufacturer's warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, DO Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. DO Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. DO Supply also makes no representations as to your right to install any such firmware on the product. DO Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Technical specifications for 1756-L1

ManufacturerAllen Bradley
CategoryPLCs
Product LineControlLogix
Part Number1756-L1
Weight0.63 lbs (0.28 kg)
Module TypeProcessor Module
User Memory64 KB
Isolation Voltage30 Volts Continuous
Communication PortOne (1) RS232
Operating Temperature32-140 Fahrenheit (0-60 Celsius)
Compatible Memory Modules1756-M1, 1756-M2 and 1756-M3
Minimum Operating Current2 milliamps at 10 Volts DC
Battery Back-Up1756-BA1; 1756-BA2
Maximum Operating Current3.5 milliamps at 30 Volts DC
Communication Cable1756-CP3
Maximum Input Current, Off-State1.5 milliamps
EnclosureOpen
Power Dissipation (Max)4.1 Watts at 60 degrees Celsius
SLot WidthOne (1)
Backplane Current at 5 Volts120 milliamps
Backplane Current at 24 Volts2 milliamps
Removeable Terminal Block(s)1756-TBCH, 1756-TBS6H
UPC10612598169532

The Allen-Bradley 1756-L1 is a ControlLogix 5550 controller. It can support up to 250 connections and weighs 0.28 kilograms or 10.0 ounces. This particular controller has a 64 Kilobytes user memory. Installing the 1756-L1 is installed directly into any slot available in the chassis and multiple controllers can be installed in any other slot within the same chassis. These controllers that belong to the same chassis, may communicate communicate with each other across the backplane as well as operate independently. The 1756-L1 has the capacity to communicate across DeviceNet, RS-232-C (DF1/DH-485 protocol), ControlNet, DH+, and EtherNet/IP networks. Note that it does not have a nonvolatile memory.

The 1756-L1 has a peak backplane current of 0.65 Amps at 5 Volts DC and 0.02 Amps at 24 Volts DC. It also has an average power dissipation of 3.3 Watts and an average thermal dissipation of 11.3 BTU/hour. The storage temperature of the 1756-L1 is from -40 to 85 Degrees Celsius, while its operating temperature ranges from 0 to 60 Degrees Celsius. It also has a noncondensing relative humidity of 5% to 95%. The storage shock of the 1756-L1 is 50 G peak for 11 milliseconds, while its operating shock is 30 G peak for 11 milliseconds. It also has a 10 to 500 Hertz vibration with a maximum peak acceleration of 2.0 G. If the 1756-L1 has a battery in need of replacement, you can only use the 1756-BA1, which is a 0.59g lithium battery. The programming cable compatible with the 1756-L1 are the category 3 serial cables 1756-CP3 and 1747-CP3.

The Allen-Bradley 1756-L1 is a Programmable Automation Controller (PAC) processor module that belongs to the ControlLogix product family. This processor belongs to one of the earlier versions of ControlLogix, the Logix 5550 category.

This module features an integrated RS232 communication port with 64KB user memory. It is also has a diagnostic front panel that reports the module’s state through embedded LED lights. delivered with a battery back-up for the integrated Random-Access Memory (RAM) however, this processor is not installed with a non-volatile memory. To install a non-volatile memory for this controller, appropriate memory modules are 1756-M1, 1756-M2 and 1756-M3 are the only compatible modules. Do not use other memory modules as this will result to module failure.

This module is installed to any ControlLogix chassis such as 1756-A4, 1756-A7, 1756-A10, 1756-A13 and 1756-A17. It occupies single slot of the chassis and module power is provided by the backplane which is energized by a ControlLogix Power supply.

This controller is capable of controlling medium scale processes. It supports IEC-61131-2 defined programming language standards such as Ladder, Function Block, Sequential Function Chart, Statement List programming languages.

The integrated RS232 provides interface to programming devices, Human Machine Interface (HMI), Supervisory Control and Data Acquisition (SCADA) and other Visualization and Control systems. It also supports stand-alone and distributed I/O allocation with the use of ControlLogix I/O, Flex I/O and POINT I/O modules.

Communication setup is defined via the RSLinx Classic or Enterprise edition where communication drivers are defined.

Revision Part #Also known as
1756-L1 Ser A1756-L1/A, Series A, Rev A
Don't see your particular revision? Contact us now.