Product image is representative; revision or series may vary. Contact us to request a specific version.
The MVI56-PDPMV1 is a Profibus DP V1 Master communication module. This module is used with the ControlLogix platform manufactured by encompass partner company, Prosoft Technology. It is a single slot module with One (1) RS485 optically isolated PROFIBUS interface supporting DP V1. It connects up to 125 Slave devices, compatible for use with PROFIBUS repeaters. It has LED status indicators and One (1) Debug / Config port.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Allen Bradley |
|---|---|
| Product Type | PROFIBUS DPV1 Master communication module |
| Product Line | ControlLogix |
| Part Number | MVI56-PDPMV1 |
| Weight | 3.00 lbs (1.36 kg) |
| Backplane Current Load | 800 ma @ 5V; 3 mA @ 24VDC |
| Compatible Controllers | ControlLogix Processors |
| Mode of operation | PROFIBUS Master |
| Compatible PROFIBUS version | Version 1 |
| No. of slave devices | 125 devices |
| No. of Ports | Two (2) ports; CFG / Debug / RS485 optically-isolated |
| Module width | Single Slot |
| Operating Shock | 30 g |
| Operating Vibration | 5 g @ 10…500 Hz |
| LED indicators | Module Status Backplane Transfer Status Application Status Serial Activity Error LED Status |
| Relative Humidity | 5% to 95% (non-condensing) |
| Slot(s) | 1 |
| Rack Type | Local or Remote |
| Data Transfer Type | Ladder Logic |
| Baud Rate | 12 Mbps max. |
| Slave Modules | 125 max. |
| Output Data | 1536 Bytes |
| Shock | 30g Operational |
| UPC | 886739898268 |
The MVI56-PDPMV1 is an ControlLogix platform compatible module. This module is a Profibus DP V1 compatible module that acts as the Master device in the Profibus network. This module is developed by Prosoft Technology, an encompass partner company of Rockwell Automation that develops Allen-Bradley PLC compatible modules.
The MVI56-PDPMV1 features One (1) RS485 port that is optically isolated, supporting PROFIBUS DP Version 1 protocol. Up to 125 PROFIBUS slave devices can be connected to this port which is also compatible with PPROFIBUS repeaters. This module has the capability of being configured up to 1536 cyclic bytes and 1536 bytes of output and supports extended diagnostic data.
Other functions supported by the MVI56-PDPMV1 include Alarm Handling, Synch and Freeze commands, Supports PROFIDrive version 3.1 parameter read and write operations, multicast and broadcast telegrams.
The MVI56-PDPMV1 has embedded LED status indicators for depicting the state of operation of the module. These LEDs indicators include Ready, Run, Error and Token indicators.
The MVI56-PDPMV1 PROFIBUS communication module is installed to a 1756 ControlLogix chassis. It occupies a single slot of the chassis and draws a current amounting to 800 mA @ 5VDC and 3 mA @ 24VDC from the backplane. It has an operating temperature of 0°C to 60°C (32°F to 140°F) and storage temperature of -40°C to 85°C (-40°F to 185°F). This module must be installed in an appropriate enclosure with vibration not exceeding 5 g from 10 Hz to 150 Hz and shock of 30 g with relative humidity of 5% to 95%, non-condensing.
The MVI56-PDPMV1 module is single slot module that fits within a 1756 backplane compatible. It is recognized as an input/output module when connected to a processor. Also, the module shifts through the processor memory in order to transfer data between the processor and module. Generally, the module serves as a PROFIBUS network scanner, a data transfer mediator for PROFIBUS devices, and a processor data memory transfer over the backplane.
The environmental conditions for the MVI56-PDPMV1 module include an operating temperature range of 0 to 60 degrees Celsius (32 to 140 degrees Fahrenheit), the storage temperature range is -40 to 85 degrees Celsius (-40 to 185 degrees Fahrenheit), 5G of vibration resistance from 10 to 150 Hertz, 30G of shock resistance (50G when not in operation) and 5 to 95% relative ambient humidity (non-condensing).
| Revision Part # | Also known as | |
|---|---|---|
| MVI56-PDPMV1 Ser A | MVI56-PDPMV1/A, Series A, Rev A | |
| Don't see your particular revision? Contact us now. | ||
Yes, the MVI56-PDPMV1 includes a free 2-year DO Supply warranty. You can upgrade to a 3-year warranty at checkout for even more protection.
The MVI56-PDPMV1 is capable of communicating up to 125 Slave devices.
The MVI56-PDPMV1 supports PROFIBUS Decentralized Peripherie (DP) version 1.
The MVI56-PDPMV1 has a backplane current load of 800 ma @ 5V and 3 mA @ 24VDC.
The ProSoft MVI56-PDPMV1 PROFIBUS DP-V1 Master Network Interface Module has 1 Slot(s) and Ladder Logic Data Transfer. The module has a Local or Remote Rack Type and a 12 Mbps max. Baud Rate.