Free UPS Ground on All Orders!
+1 (919) 205-4392
Allen Bradley FLEX 5000 5094-OW8I

Product image is representative; revision or series may vary. Contact us to request a specific version.

5094-OW8I

|

The Allen-Bradley 5094-OW8I output module from the Flex 5000 series is an isolated relay output module. It has 8 isolated relay output channels. The 5094-OW8I isolated relay output module can operate with AC voltage and with DC voltage. Its AC voltage range is from 5 to 240 Volts AC and its DC voltage range is from 5 to 125 Volts DC. The 5094-OW8I isolated relay output module has a maximum power dissipation rating of 3.5 Watts and a maximum thermal dissipation rating of 11.94 BTU per hour.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more
Rockwell Disclaimer: The product is used surplus. DO Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because DO Supply is not an authorized distributor of this product, the Original Manufacturer's warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, DO Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. DO Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. DO Supply also makes no representations as to your right to install any such firmware on the product. DO Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Technical specifications for 5094-OW8I

ManufacturerAllen Bradley
CategoryPLCs
Product LineFLEX 5000
Part Number5094-OW8I
UPC889508097619
Weight0.44 lbs (0.20 kg)
Module TypeSafety Digital 4-point Isolated Relay Output Module
Relay rating2 A resistive/channel @ 5...30V DC 2 A resistive/channel @ 5...240V AC, 50/60 Hz 2 A general/channel @ 5...240V AC, 50/60 Hz 2 A ATEX/IECEx @ 5...240V AC, 50/60 Hz
Off-state leakage0 mA (dry contact, no onboard snubbers)
Output current rating, max2 A per channe
Output delay time, max for Off to On and On to Off10 ms 10 ms
Initial contact resistance, max30 mΩ
Bounce time, mean500 μs
Output control in fault state per poin•Hold last state •On •Off (default
Output states in program mode per point•Hold last state •On •Off (default)
Output states in fault mode per point•Hold Last State•On•Off (default)
Duration of fault mode per poin•1 s •2 s •5 s •10 s •Forever (default)
Delay to faultSupported

The Allen-Bradley 5094-OW8I standard FLEX 5000 I/O module is made to connect to Allen-Bradley industrial controllers with version 31 of the Logix Designer Application such as the GuardlLogix 5580, ControlLogix 5580, Compact GuardLogix 5380, and the CompactLogix 5380 controllers. This I/O module is an 8-point I/O module that has 8 isolated and normally open relay outputs. It is rated for 5 to 240 Volts AC voltage or 125 Volts DC voltage. It operates at a frequency of 50 to 60 Hertz. When the 5094-OW8I I/O module is being programmed and when it is in the Communication Fault mode, its individual output points can be configured into specific states. These configurable output starts are the off-state, the on-state, and “Hold the Last State.” It takes the outputs about 10 milliseconds to change their states.

The Allen-Bradley 5094-OW8I standard FLEX 5000 I/O module comes with built-in internal electrical isolation between its system-side power bus and its field-side power bus. This module has status indicators for each of its outputs that let the users know the status of the outputs as they operate. These indicators can be yellow or red depending on the status of the output. There are also status indicators for the whole module and for the power. The output current rating for each of the 8 output channels is 2 Amps. If the 5094-OW8I I/O safety module does not have any snubbers on it, the off-state leakage current rating is 0 milliamps.