Technical Specifications for 100-E460EN11
Brand | Allen-Bradley / Rockwell Automation |
Series | IEC 100 Contactors |
Part Number | 100-E460EN11 |
Number of Poles | 3 |
Type of Product | Direct-On-Line Contactor |
Rated isolation voltage (AC-3) | 400 Volts |
Rated Isolation voltage (AC-1) | 690 Volts |
Rated operational current at 400 Volts (AC-3) | 460 Amps |
Rated operational current at 690 Volts (AC-1) | 700 Amps |
Ratings for switching AC motors at 220 to 240 Volts | 132 kilowatts |
Ratings for switching AC motors at 380 to 400 Volts, 415 Volts and 440 Volts | 250 kilowatts |
Ratings for switching AC motors at 500 Volts | 315 kilowatts |
Ratings for switching AC motors at 690 Volts | 355 kilowatts |
Ratings for switching AC motors at 1000 Volts | 280 kilowatts |
Auxiliary Contacts | 1 N.O.,1 N.C. |
Coil Voltage | 250 to 500 Volts AC/DC |
AC Voltage Frequency | 50 to 60 Hertz |
Brand | Allen-Bradley / Rockwell Automation |
Series | IEC 100 Contactors |
Part Number | 100-E460EN11 |
Number of Poles | 3 |
Type of Product | Direct-On-Line Contactor |
Rated isolation voltage (AC-3) | 400 Volts |
Rated Isolation voltage (AC-1) | 690 Volts |
Rated operational current at 400 Volts (AC-3) | 460 Amps |
Rated operational current at 690 Volts (AC-1) | 700 Amps |
Ratings for switching AC motors at 220 to 240 Volts | 132 kilowatts |
Ratings for switching AC motors at 380 to 400 Volts, 415 Volts and 440 Volts | 250 kilowatts |
Ratings for switching AC motors at 500 Volts | 315 kilowatts |
Ratings for switching AC motors at 690 Volts | 355 kilowatts |
Ratings for switching AC motors at 1000 Volts | 280 kilowatts |
Auxiliary Contacts | 1 N.O.,1 N.C. |
Coil Voltage | 250 to 500 Volts AC/DC |
AC Voltage Frequency | 50 to 60 Hertz |
s
About 100-E460EN11
The 100-E460EN11 contactor is an IEC 100 series direct-on-line contactor that has been designed and manufactured by Allen-Bradley/Rockwell Automation. The unit is part of the 100-E product series and it is made in accordance with standards like the CCC, UL, cULus, EAC, CSA, RCM, KC, CE, and similar standards. The 100-E460EN11 contactor uses an ambient temperature range of -40 to 70 degrees Celsius (-40 to 158 degrees Fahrenheit) for standard operation. The specified operating temperature range for storage is the same as the one for operation. The 100-E460EN11 direct-on-line contactor has a Category B climatic withstand rating according to the IEC 60947-1 (Annex Q) standards and it can operate at a maximum altitude of 3000 meters.
The 100-E460EN11 contactor has 3 poles and a rated isolation voltage of 400 Volts (AC-3) and 690 Volts (AC-1). In addition to that, the rated isolation voltage according to the IEC standards is 1000 Volts and it is 600 Volts according to the UL and CSA standards. The 100-E460EN11 contactor has a rated impulse voltage of 8 kilovolts and it is built in accordance with the IEC 60947-1 (Environment A and B) standard for electromagnetic compatibility. The 100-E460EN11 contactor is an IP 00 rated unit but its contactor coil terminals and auxiliary contacts can have an IP2X protection rating in a connected state. The 100-E460EN11 contactor has 1 N.O. and 1 N.C. auxiliary contacts and it features a coil voltage range of 250 to 500 Volts AC/DC with 50 to 60 Hertz AC frequency. The rated current of the unit ranges from 460 to 700 Amps, depending on the voltage source. The output power ratings for switching AC motors with the 100-E460EN11 contactor are 132 to 355 kilowatts and 150 to 500 Horsepower.
Repair Services for 100-E460EN11
Type |
Lead Time |
Price |
Action |
Repair Service |
2-4 weeks |
Ask | Get Quote |
Our highly skilled technicians can repair your 100-E460EN11. All of our repairs come with a 1 Year DO Supply Warranty. Please contact us for additional information about our repair process.