The W200MLCFC is a 3-Phase, Non-Reversing Magnetic Motor Starter that is manufactured by Eaton / Cutler Hammer. This is part of the advantage series that is designed for motor voltage of 200 Volts AC, 200-575 Volts AC, 3-Phase and coil voltage of 120 Volts AC @ 60 Hertz and 110 Volts AC @ 50 Hertz. It has a continuous output current of 27 Amperes with an output power of 7.5 Horsepower @ 200 Volts AC and 230 Volts AC; 10 Horsepower @ 460 Volts AC and 575 Volts AC.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for W200MLCFC

ManufacturerEaton Cutler-Hammer
CategoryDrives
Product LineW200 Drives
Part NumberW200MLCFC
Weight10.00 lbs (4.54 kg)
SeriesAdvantage
Product DescriptionNon-reversing magnetic starter
SizeNEMA Size 1
Coil Voltage120 VAC @ 60 Hz; 110 VAC @ 50 Hz
Motor Voltage200 VAC; 230 VAC; 460 VAC; 575 VAC
Continuous output current27 A
Output power7.5 HP @ 200 VAC and @ 230VAC; 10 HP @ 460 VAC and 575 VAC
No. of Poles3
Motor Protection FeaturesOverload; Ground current sensing; Phase unbalance; Phase Loss
Phase Trip setting1.15 A
Ground Current trip setting10:00 AM
Overload ClassClass 10, 20, 30

The W200MLCFC is a motor starter manufactured by Eaton Cutler-Hammer. The starter has 3 poles and it is used with motors that have a Horsepower rating of 1 Horsepower when the starter is being operated with an input voltage of 230 Volts AC. When it is being operated with an input voltage of 460 Volts AC, the W200MLCFC can be used with a motor that has a Horsepower rating of 2 Horsepower. The W200MLCFC accommodates an input voltage that is supplied by a 3-phase source. The current rating for the W200MLCFC is capped at 27 Amps. The Eaton Cutler-Hammer W200MLCFC has a NEMA size 1 rating. The starter is capable of starting, stopping, and interrupting the locked rotor current of the motors that it controls. To protect the W200MLCFC from short circuits, motor branch protection must be provided. Additionally, to prevent device damage and injury to the users, the W200MLCFC must be installed, maintained, and operated by qualified users.

The W200MLCFC belongs to the non-reversing category of the Advantage series of motor starters from Eaton Cutler-Hammer. The W200MLCFC operates at a frequency of 60 Hertz. If the starter’s circuit board needs to be replaced, the WCBSLF replacement circuit board can be used. Additionally, the W200MLCFC, like other motor starters in the Advantage series, helps the motors to have an extended operating life.

The W200MLCFC is an Eaton Corporation / Cutler Hammer manufactured non-reversing motor starter. This motor starter mainly features a continuous output current of 27 Amperes (enclosed) and 30 Amperes (open) and a coil voltage of 120 Volts AC @ 60 Hertz and 110 Volts AC @ 50 Hertz.

If used with a Squirrel Cage motor, this motor starter has a rated output power of 7.5 Horsepower @ 200 Volts AC and 230 Volts AC; 10 Horsepower @ 460 Volts AC and 575 Volts AC. For Resistive heating, 3-Phase, 3-pole wiring, it provides 5 kilowatts @ 120 Volts AC; 10 kilowatts @ 240 Volts AC; 20 kilowatts @ 480 Volts AC and 25 kilowatts @ 600 Volts AC. For transformer switching, 3-Phase and 3-Pole wiring, it delivers 3.6 kVA @ 208 VA; 4.3 kVA @ 240 VAC; 8.5 kVA @ 480 VAC and 11 kVA @ 600 V.

The W200MLCFC has embedded protection functions such as Ground Current Sensing Protection, Phase Unbalance and Phase Loss. All these functions can be omitted using the Advantage Programming Module (WAPM). Being a NEMA size 1 motor starter, this device has Ground current senting value of 10 Amperes, lockout Current of 24 Amperes and a trip time of 0.4 seconds. For Phase trip time, phase level unbalance is detected @ 30% with a trip delay of 6 seconds while Phase loss trip is triggered after 2 seconds when current is below 1.15 Amperes.

The W200MLCFC AC coil has Inrush VA of 250 VA with Closed VA of 25 VA and Closed Watts @ 5 Watts. It has Pick-Up volts of 78 VAC and Drop out Volts @ 60 VAC.