The Eaton Cutler-Hammer HFDE308036L is an electronic circuit breaker that operates efficiently within a rated voltage of 600 VAC and 250 VDC. This unit features a robust rated current of 80 A and is designed with three poles, offering versatile protection in various applications.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Eaton Cutler-Hammer |
|---|---|
| Product Type | Electronic Circuit Breaker |
| Product Line | Series C Circuit Breakers |
| Part Number | HFDE308036L |
| Weight | 4.50 lbs (2.04 kg) |
| UPC | 786685112749 |
| Rated Voltage (AC) | 600 VAC |
| Rated Voltage (DC) | 250 VDC |
| Rated Current | 80 A |
| Number of Poles | 3 Poles |
| Trip Type | Electronic Digitrip RMS 310 |
| Trip Functions | LSIG (Long-time, Short-time, Instantaneous, Ground fault) |
| Interrupt Rating at 240 VAC | 100 kAIC |
| Interrupt Rating at 480 VAC | 65 kAIC |
| Interrupt Rating at 600 VAC | 25 kAIC |
| Terminal Type | Line and Load Terminals |
The HFDE308036L model from Eaton Cutler-Hammer is classified as an electronic circuit breaker, engineered for both efficiency and reliability. It can handle a rated voltage of up to 600 VAC and a DC voltage of 250 V. With a current rating of 80 A, this breaker is equipped with three poles, making it suitable for various circuit protection applications.
For advanced protection, it integrates the Electronic Digitrip RMS 310 trip type, which effectively manages multiple trip functions including long-time, short-time, instantaneous, and ground fault. This functionality allows for comprehensive monitoring and response to electrical faults.
In terms of interrupt ratings, this circuit breaker showcases impressive performance—100 kAIC at 240 VAC ensures it can handle significant fault currents. Additional ratings include 65 kAIC at 480 VAC and 25 kAIC at the maximum rated voltage of 600 VAC. Such high interrupt ratings make it suitable for demanding environments where electrical safety is paramount.
The HFDE308036L model uses line and load terminals to facilitate straightforward installation and connection to existing electrical systems. Overall, this electronic circuit breaker represents an important solution for protecting circuits and providing vital safety features in diverse applications.