Eaton Cutler-Hammer Series C Circuit Breakers LDC3400

Product image is representative; revision or series may vary. Contact us to request a specific version.

LDC3400

|

The LDC3400 from Eaton Cutler-Hammer is a robust molded case circuit breaker fashioned for reliable circuit protection. With a rated current of 400 A and designed for three-phase applications, it ensures efficient operation under high-demand conditions.

Call for an immediate quote
2 Year DO Supply Warranty
Available
Ships from Raleigh, NC
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for LDC3400

ManufacturerEaton Cutler-Hammer
Product TypeMolded Case Circuit Breaker
Product LineSeries C Circuit Breakers
Part NumberLDC3400
Weight21.00 lbs (9.53 kg)
Rated Current400 A
Number of Poles3 Poles
Phase Type3 Phase
Voltage Rating (AC)600 VAC
Voltage Rating (DC)250 VDC
Interrupting Capacity (240 VAC)200 kAIC
Interrupting Capacity (480 VAC)100 kAIC
Interrupting Capacity (600 VAC)50 kAIC
Interrupting Capacity (250 VDC)22 kAIC
Trip TypeThermal-Magnetic
Trip FunctionsLong-Time and Instantaneous (LI)
Min. Frequency50 Hz
Max. Frequency60 Hz

Eaton Cutler-Hammer presents the LDC3400 molded case circuit breaker, a vital component in contemporary electrical systems. This unit is rated at 400 A and is structured with three poles, ideal for managing three-phase applications. It meets rigorous voltage requirements with an AC rating of 600 VAC and a DC rating of 250 VDC.

The LDC3400 is equipped with significant interrupting capacities—200 kAIC for 240 VAC, 100 kAIC for 480 VAC, and 50 kAIC for 600 VAC. For DC applications, it can handle interruptions up to 22 kAIC at the 250 VDC level, ensuring robust protection against fault currents.

This device utilizes a thermal-magnetic trip mechanism, incorporating both long-time and instantaneous (LI) trip functions for enhanced reliability during varying electrical conditions. It operates effectively within a frequency range from a minimum of 50 Hz to a maximum of 60 Hz, making it well-suited for standard industrial power systems.

Overall, the LDC3400 provides both protection and performance, making it a critical asset wherever reliable circuit management is essential.