Product image is representative; revision or series may vary. Contact us to request a specific version.
The JGE3250FAG molded case circuit breaker from Eaton Cutler-Hammer is designed for reliability in electrical systems. With a rated current of 250 A, it operates effectively at a maximum voltage of 600 VAC and features three poles.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Eaton Cutler-Hammer |
|---|---|
| Product Type | Molded Case Circuit Breaker |
| Product Line | Series G Circuit Breakers |
| Part Number | JGE3250FAG |
| Weight | 6.00 lbs (2.72 kg) |
| UPC | 782113526768 |
| Rated Current | 250 A |
| Voltage Rating | 600 VAC |
| Number of Poles | 3 Poles |
| Trip Type | Fixed Thermal, Adjustable Magnetic |
| Interrupt Rating (240 VAC) | 65 kAIC |
| Interrupt Rating (480 VAC) | 25 kAIC |
| Interrupt Rating (600 VAC) | 18 kAIC |
| Terminal Connection | Line and Load Side |
| Minimum Frequency | 50 Hz |
| Maximum Frequency | 60 Hz |
The Eaton Cutler-Hammer JGE3250FAG is a molded case circuit breaker ideal for circuit protection and control in demanding environments. It is rated for a current of 250 Amperes and functions with a maximum voltage of 600 VAC. This design incorporates three poles, ensuring compatibility with multi-phase systems.
The trip mechanism of this model includes fixed thermal protection alongside adjustable magnetic settings, which allows for customization based on specific electrical loading conditions. Concerning fault protection, the JGE3250FAG features substantial interrupting capacities: it can handle up to 65 kAIC at 240 VAC, 25 kAIC at 480 VAC, and 18 kAIC at the maximum voltage rating of 600 VAC.
Weighing in at 6 lbs, this circuit breaker includes terminals for both line and load side connections which facilitate ease of installation and ensures reliable performance. The device is also functional across a frequency range of 50 Hz to 60 Hz, making it suitable for various operational scenarios.