GE Fanuc Emerson Series 90-30 IC693MDL916

Product image is representative; revision or series may vary. Contact us to request a specific version.

IC693MDL916

|

The IC693MDL916 is a Series 90-30, relay output module. This module features Sixteen (16) individually isolated Form A relay outputs. Each relay contact has maximum current rating of 4 Amperes and operable at voltage ranges of 5-125 VDC / 5-250 VAC. It has backplane power consumption of 300 mA from the 5VDC backplane.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for IC693MDL916

ManufacturerGE Fanuc Emerson
Product typeDigital I/O
Product LineSeries 90-30
Part NumberIC693MDL916
Weight0.63 lbs (0.28 kg)
CompatibilityGE Fanuc 90-30 PLCs
Product DescriptionRelay Output module
Output points16
No of ChannelsSixteen (16)
Output typeForm A Relays
Output groupingsIndividually isolated channels
LED indicatorsYes
Contact formForm A contacts (Normally Open (N.O.)
Field to backplane isolation250 Volts AC continuous
Maximum output current4:00 AM
Minimum output current10 milliamps
Operating voltages5-125 VDC / 5-250 VAC
Peak switching frequency20 cycles / minute
Switching Frequency20 Cycles per minute
Product Lifecycle Status*Discontinued/Obsolete
Nominal output voltage12 / 24 VDC
Current draw300 mA at 5VDC
Compatible connectorsIC694TBBx32 / IC694TBSx32
Module widthSingle slot
Product lifecycleObsolete

* The GE Fanuc Emerson IC693MDL916 has been discontinued by the manufacturer, however we specialize in obsolete parts and can likely still supply surplus and/or refurbished replacement IC693MDL916 units instead of migration.

The IC693MDL916 is a relay output module that is part of the GE Fanuc Series 90-30 Programmable Logic controller. This module is a single-slot width module that features Sixteen (16) individually isolated Form A or Normally Open (N.O.) contacts. Each contact output of this module has maximum output current rating of 4 Amperes and is operable with both AC and DC voltages specifically, 5-125 VDC / 5-250 VAC. The IC693MDL916 is a single slot module that mounts to a series 90-30 baseplate. It consumes a single slot of the and supports functioning as a local and distributed I/O component. Install as many IC693MDL916 modules as needed, limited only by the I/O capability, memory capacity, and available installation slots of the Series 90-30 system. Also, the IC693MDL916 may act as distributed I/O component of the modern PAC system RX3i and RX7i Programmable Automation Controller (PAC) platform. The IC693MDL916 has a backplane power consumption of 300 mA from the 5VDC backplane. It requires the use of a High-Density Terminal Block. With individually isolated contact outputs, maximum operation flexibility can be achieved as mixing of DC and AC signals is allowed. The maximum switching frequency of each contact output channel is 20 cycles per minute. Provided with the module are DIP switches that are used to configure the module’s reaction when the CPU transitions to Stop mode. In addition, the module’s default mode set via the DIP switch must be the similar to configuration created in the programming software. Compatible connectors for use with this module are IC694TBBx32 or IC694TBSx32.

The GE Fanuc Series 90-30 IC693MDL916 output module is a 16-point relay output module. It provides 16 Form A relays for controlling loads that are connected to the module outputs. The IC693MDL916 output module can be used with either GE Fanuc Series 90-30 PLCs or with the GE PACSystems RX3i systems. The IC693MDL916 output module can be used with different terminal blocks, including extended spring-style, regular spring style, extended box style, and regular box style terminal blocks. The DIP switch on the back side of the IC693MDL916 output module can be used to change the default mode to the Hold Last State mode or to activate the Force OFF function to power the module down forcibly. The DIP switch configuration can be performed after the module is removed from the backplane. Individually numbered LEDs are provided on the front of the module to indicate status of the module outputs. The power consumption rating of the IC693MDL916 relay output module is 150 milliamps of current at 24 Volts DC from the backplane and it is 300 milliamps of current at 5 Volts DC from the backplane. The field to backplane isolation is 250 Volts AC continuous and 1550 Volts AC for 1 minute. The output current is a minimum of 10 milliamps per point, 4 Amps for 5 to 250 Volts AC, 4 Amps for 5 to 30 Volts DC, 200 milliamps for 125 Volts DC, 2 Amps of pilot duty per output, and 2 Amps of load per output. The maximum switching frequency is 20 cycles per minute. The DIP switch on the module determines the output operation for the stop mode on the CPU and it determines when the CPU is not able to communicate with the module. The default mode for the outputs that is set through the DIP switch must be the same as the default mode that is configured through the software configuration process.

Revision Part #Also known as
IC693MDL916AAIC693MDL916-AA, Series AA, Rev AA
IC693MDL916CAIC693MDL916-CA, Series CA, Rev CA