Product image is representative; revision or series may vary. Contact us to request a specific version.
The IC697ALG321 Analog Input Module is a 4-channel analog voltage input module made by GE Fanuc. It runs with -10 to +10 Volts, it has 16 bits of resolution, and it has a 2-millisecond conversion rate.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | GE Fanuc Emerson |
|---|---|
| Product Line | Series 90-70 |
| Part Number | IC697ALG321 |
| Weight | 1.63 lbs (0.74 kg) |
| Product Description | Analog Input Module |
| No. of Inputs | 4 Inputs |
| Voltage Input Range | -10 to +10 Volts |
| Conversion Rate | 2 ms |
| Resolution | 16 bits with 14-bit monotonicity |
| Calibration | Factory set at 10 Volts +/- 2 mV |
| Input Impedance | 250 Ohms |
| Power Requirement | 112 milliamps at +5 Volts |
The IC697ALG321 Analog Input Module is a high-level analog voltage input module from GE Fanuc. It belongs to the Series 90-30 product line of GE PLCs or Programmable Logic Controllers. It allows for both unipolar and bipolar voltage input ranges. The users can also set alarm limits for both ranges such as the alarm high limit or the alarm low limit. The MS-DOS configuration software provides all the facilities needed to configure the module parameters for their hosts systems such as channel configuration, mode selection, alarm settings, range selection, and I/O scan set configuration facilities. The converted analog data is stored on the CPU of the PLC in the 2’s complement format. It also has status bits, which are returned back to the CPU of the PLC to provide data about the module's operation.
The IC697ALG321 Analog Input Module has an input filter response frequency of 41 Hertz for the single-ended mode and 82 Hertz for the differential mode. The received data signal will be converted to a digital signal through a 12-bit converter so that it can be processed in the CPU of the PLC. In order to gain resolution and accuracy, this converted data will also be placed inside a 16-bit WORD format. The CPU does not change any of the received values from the inputs and it directly converts and processes the signal as required before placing inside the WORD format. The users can use the interface provided by the Logicmaster software or a handheld programmer to perform the basic configuration of the module easily. Note that the handheld programmer does not provide the facilities to configure the scanned channels that are active. All the configuration data will be saved in the EEPROM of the CPU in the PLC.
| Revision Part # | Also known as | |
|---|---|---|
| IC697ALG321A | IC697ALG321-A, Series A, Rev A | |
| Don't see your particular revision? Contact us now. | ||