Product image is representative; revision or series may vary. Contact us to request a specific version.
The IC610MDL185 is an output module from GE Fanuc Emerson's Series One. It features six outputs for control purposes. It operates at a voltage rating of 115 Volts AC and has a defined voltage range of 97 to 132 volts.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | GE Fanuc Emerson |
|---|---|
| Product Type | Output Module |
| Product Line | Series One |
| Part Number | IC610MDL185 |
| Weight | 2.00 lbs (0.91 kg) |
| Number of Outputs | 6 Outputs |
| Voltage Rating | 115 Volts AC |
| Operating Voltage Range | 97 to 132 Volts AC |
| AC Frequency | 47 to 63 Hertz |
| Maximum Current per Point | 0.5 Amps |
| Maximum Leakage Current | 0.5 mA at 110 Volts AC and 60 Hertz |
| Smallest Recommended Current Load | 25 mA |
| Maximum Inrush for 16 ms | 10 Amps |
| Maximum Inrush at 100 ms | 5 Amps |
| Internal Power Consumption | 2 mA per ON Circuit at 9 Volts DC |
In industrial automation, the GE Fanuc Emerson IC610MDL185 provides solid functionality as an output module. This device has six outputs, delivering precise control in various applications. It is rated at 115 volts AC and operates efficiently within a range of 97 to 132 volts AC for flexibility. Additionally, this output module has an AC frequency capability between 47 and 63 Hertz.
Each output is limited to a maximum current of 0.5 Amps, ensuring reliable and safe operation. It is crucial to note that the module supports a minimum recommended load of 25 mA for optimal performance. For transient conditions, the IC610MDL185 can handle an impressive maximum inrush current of 10 Amps when active for up to 16 milliseconds and up to 5 Amps for an extended period of 100 milliseconds. Furthermore, this module has a maximum leakage current of 0.5 mA at standard operating conditions of 110 volts AC and a frequency of 60 Hertz.
With an internal power consumption of just 2 mA per ON circuit at 9 volts DC, the IC610MDL185 ensures that it operates efficiently while managing output needs. This module's specifications highlight its strengths in various applications within the automation framework.