The IC600YB813 is a thermocouple input module within the GE Fanuc Emerson Series Six line, specifically designed for Type J thermocouples. It effectively measures a temperature span from -100 to 760 °C, with an input voltage range of -4.632 to 42.922 mV.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | GE Fanuc Emerson |
|---|---|
| Product Type | Type J Thermocouple Input Module |
| Product Line | Series Six |
| Part Number | IC600YB813 |
| Weight | 6.00 lbs (2.72 kg) |
| Input Type | Thermocouple Inputs |
| Input Voltage Range | -4.632 to 42.922 mV |
| Thermocouple Temperature Range | -100 to 760 °C |
| Rated Accuracy | ±1.3 °C |
| Resolution | 13 Bits |
| Cold Junction Compensation | Supported |
| Open Thermocouple Detection | Supported |
| Sample Rate | Adjustable with Jumpers |
| Normal Mode Rejection | 86 dB at Line Frequencies |
| Calibration Interval | Every 6 Months |
| Data Processing | Onboard Microprocessor |
The IC600YB813 from GE Fanuc Emerson is a Type J thermocouple input module tailored for the Series Six lineup. This module is capable of measuring temperatures ranging from -100 °C to 760 °C. It operates with an input voltage spanning -4.632 to 42.922 mV, ensuring it can respond effectively to various thermocouple signals.
This device delivers a rated accuracy of ±1.3 °C, suitable for demanding temperature monitoring applications. Additionally, it achieves a resolution of 13 bits, allowing for precise temperature readings. The module supports cold junction compensation and the detection of open thermocouples, which are critical for maintaining measurement integrity.
Users can adjust the sample rate with jumpers, providing flexibility for different application needs. The module also demonstrates robust normal mode rejection characteristics, rated at 86 dB under line frequencies, enhancing its reliability in electrically noisy environments. To maintain performance, a calibration interval of every six months is recommended. Data processing is managed by an onboard microprocessor, allowing for efficient handling of measurement tasks.