| Manufacturer | GE Fanuc Emerson |
|---|---|
| Product Line | Series Six |
| Part Number | IC600YB904 |
| Weight | 6.00 lbs (2.72 kg) |
| Module Type | AC Output Module |
| Power Requirement | 5V DC, 535 mA, max. |
| Voltage Rating | 90 to 130V AC |
| Nominal Voltage | 115V AC |
| Leakage Current (OFF) | 1.7 mA at 115V AC |
| On-State Current | 2 Amps, max. |
| On-State Voltage Drop | 1.5 Volts (Typical), 2.5 Volts (Maximum) |
| Relative Humidity | 5 to 95% (Non-Condensing) |
| Storage Temperature | -20 to 80 degrees Celsius |
| Inrush Current | 12 Amps for 33 ms |
| Operating Temperature | 0 to 60 degrees Celsius |
The IC600YB904 module, part of GE Fanuc Emerson's Series Six, is an AC output module crafted for reliable performance in various applications. It accommodates voltage levels in the 90 to 130-volt AC range, enabling effective operation at a nominal voltage of 115 volts.
This unit requires a power input of 5V DC and draws a maximum current of 535 mA. When deactivated, it experiences a leakage current of 1.7 mA at the nominal voltage of 115 volts AC. During operation, the module can handle a maximum on-state current of up to 2 amps, essential for driving connected loads.
The on-state voltage drop is typically measured at 1.5 volts, with a peak of 2.5 volts under maximum load conditions. This module can effectively manage high initial currents with an inrush current capability of 12 amps for 33 milliseconds.
It is designed to maintain operational stability in environments with relative humidity between 5 and 95%, provided no condensation exists. Regarding temperature tolerance, the IC600YB904 functions within an operating temperature range of 0 to 60 degrees Celsius. It can be stored in conditions from -20 to 80 degrees Celsius, ensuring versatility across different industrial settings.