Product image is representative; revision or series may vary. Contact us to request a specific version.
The IC610MDL155 from GE Fanuc Emerson serves as an output module within the Series Six lineup. This model encompasses a total of eight outputs, operating at a nominal voltage of 24 volts DC, with continuous output current capabilities reaching 0.5 amps.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | GE Fanuc Emerson |
|---|---|
| Product Type | Output Module |
| Product Line | Series Six |
| Part Number | IC610MDL155 |
| Weight | 2.00 lbs (0.91 kg) |
| Number of Outputs | 8 |
| Output Voltage | 24 Volts DC |
| Output Current | 0.5 Amps (Continuous) |
| Fuse Rating | 3 Amps |
| Maximum Current Consumption | 30 milliamps at 9 Volts DC |
| Operating Temperature Range | 0 to 60 degrees Celsius (at outside of rack) |
| Maximum On-State Outputs at 50°C | 8 |
| Maximum On-State Outputs at 60°C | 6 |
| Maximum Output Voltage | 40 Volts DC |
| On-State Voltage Drop at 0.5 Amps | 1 Volt |
| On-State Voltage Drop at 0.1 Amps | 0.75 Volts |
| Minimum Load | 1 milliamp |
The IC610MDL155 output module, part of the GE Fanuc Emerson Series Six, is engineered for reliable performance in automation applications. This module offers eight distinct outputs, each delivering 24 volts DC, facilitating enhanced control over connected devices or systems. For continuous operation, it supports output currents of up to 0.5 amps, which suits various operational demands.
The fuse rating for this unit is 3 amps, providing a safety margin during operation. Maximum current draw, when functioning at 9 volts DC, caps at 30 milliamps, reflecting its efficient power management. Weighing around 120 grams, the module features a compact design, allowing for straightforward integration into existing setups.
Operating temperatures for the IC610MDL155 range from 0 to 60 degrees Celsius when placed outside the protection of a rack. The maximum number of on-state outputs varies with temperature; it can maintain up to eight outputs at 50°C while this number decreases to six at 60°C. Its maximum output voltage capability reaches 40 volts DC, ensuring compatibility with various load requirements.
The on-state voltage drops are also noteworthy; 1 volt at a current of 0.5 amps and 0.75 volts at 0.1 amps ensures effective power delivery while maintaining performance. A minimum load of merely 1 milliamp ensures that the module can respond effectively even under low load conditions, making it versatile for numerous control applications.