Free UPS Ground on All Orders!
+1 (919) 205-4392
Horner Electric APG HE693PBS105

Product image is representative; revision or series may vary. Contact us to request a specific version.

HE693PBS105

|

The HE693PBS105 is a specialized Profibus DP slave module from Horner Electric’s APG series. This module operates reliably with a steady-state power requirement of 3 W at 5 VDC and supports communication for up to 64 slave devices within a segment. It accommodates baud rates ranging from 9.6 kbps up to 12 Mbps and connects via a 9-pin D-sub connector for the DP port.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for HE693PBS105

ManufacturerHorner Electric
Product TypeProfibus DP Slave Module
Product LineAPG
Part NumberHE693PBS105
Weight0.50 lbs (0.23 kg)
Required Power (Steady-State)3 W @ 5 VDC
Input/Output SupportSlave devices up to 64 in segment
Baud Rates Supported9.6 kbps to 12 Mbps
Connector Type9-pin D-sub for DP port
Network TypeProfibus DP (Master-Slave)
Slot UsageSeries 90-30 I/O rack slot
IsolationField-to-logic approx. 1500 VAC
Max Devices per SegmentUp to 32 without repeaters, 64 with repeaters
Update/Scan MechanismPolled & explicit messaging (Profibus DP)
Data InterfaceBackplane I/O bus & Profibus DP network
Operating Temperature0–60 °C
Storage Temperature-40–85 °C
Relative Humidity5–95% non-condensing

The HE693PBS105 Profibus DP slave module from Horner Electric is designed to enhance communication in automated systems. Operating with a steady-state power consumption of only 3 W at 5 VDC, it efficiently manages connections for a range of devices.

This module effectively supports a robust input/output configuration, allowing for the addition of slave devices up to 64 in a segment, ensuring scalability in system design. It features a baud rate range from 9.6 kbps to 12 Mbps, which caters to various data transmission needs.

Integration is straightforward with a 9-pin D-sub connector for the DP port, making it an ideal fit for series 90-30 I/O rack slots. The design includes isolation of approximately 1500 VAC from field to logic, ensuring protection against voltage spikes and safeguarding sensitive components.

The HE693PBS105 can support a total of 32 devices without repeaters and can extend to 64 devices when repeaters are implemented, providing flexibility in larger systems. It employs a combination of polled and explicit messaging for updates and scans, optimizing communication efficiency within Profibus DP networks.

Reliable performance is maintained within an operating temperature range of 0 to 60 °C and can withstand storage temperatures as low as -40 °C and as high as 85 °C. Tolerance to relative humidity is also robust, functioning effectively within a 5 to 95% non-condensing range, making it suitable for a variety of industrial environments.