Product image is representative; revision or series may vary. Contact us to request a specific version.
The FA-TC9102-0221 model from Johnson Controls is a Direct Digital Controller (DDC) designed for efficient heating and cooling management. The unit features proportional control from 0 to 10 VDC and has an on/off relay for fan operation.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Johnson Controls |
|---|---|
| Product Line | Metasys FA |
| Part Number | FA-TC9102-0221 |
| Weight | 3.00 lbs (1.36 kg) |
| Unit Type | Direct Digital Controller |
| Fan Control | On/Off Relay |
| Heating/Cooling Control | 0 to 10 VDC Proportional |
| N2 Bus | Opto-isolated |
| Operating Environment Rating | 32 to 122°F (0 to 50°C), 10 to 90% RH non-condensing |
| I/O Terminations | Screw terminal block |
| AI Remote Setpoint | Active 3-wire, Pot, at 0 to 10K ohms |
| BO Heating/Cooling Control | Triac rated at 0.5A at 24V AC |
| BO Fan Control | Relay rated at 3A at 125/250 VAC, with 1/8 hp maximum |
| AO Heating/Cooling Control and Fan Control | 0 to 10V DC and 10 mA |
The Johnson Controls FA-TC9102-0221 is a Direct Digital Controller primarily designed for HVAC applications. It ensures precise temperature regulation through its proportional control capabilities, which operate through a voltage range of 0 to 10 VDC. Fan control is managed via an On/Off relay, enabling users to maintain optimal airflow as needed.
The device's operational range makes it suitable for environments with temperatures from 32°F to 122°F (0°C to 50°C) and can handle relative humidity conditions of 10% to 90% without condensation affecting performance. Communication features include an opto-isolated N2 bus, contributing to operational integrity within a larger system of controllers.
Connections for input and output are facilitated via screw terminal blocks, simplifying the wiring process for integration into existing setups. The active 3-wire configuration for remote setpoints can accommodate pots in the 0 to 10K ohm range, facilitating adjustments from a distance.
For output control, the heating and cooling requirements are managed through a triac with a capacity of 0.5A at 24V AC, ensuring reliable operation in various conditions. Additionally, fan control employs a relay rated at 3A for voltages between 125 to 250 VAC, capable of handling a maximum motor rating of 1/8 horsepower. Overall, the FA-TC9102-0221 Direct Digital Controller is equipped to efficiently manage heating, cooling, and ventilation systems.