Product image is representative; revision or series may vary. Contact us to request a specific version.
The Johnson Controls part number T-5312-1 is a pneumatic receiver-controller known for its precise control capabilities. This unit operates under a proportional control type and manages output signal pressure between 3 to 15 psig.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Johnson Controls |
|---|---|
| Product Type | Pneumatic receiver-controller |
| Product Line | Other |
| Part Number | T-5312-1 |
| Control Type | Proportional |
| Output Signal Pressure | 3 to 15 psig |
| Maximum Supply/Signal Pressure | 25 psig |
| Operating Temperature Range | -28.9°C to 65.6°C |
| Body Material | Aluminum |
| Cover Material | Zinc |
| Mounting Type | Surface mounting |
| Control Action | Field-selectable direct acting (DA) or reverse acting (RA) |
| Port Connections | 1/4-inch barbed fitting (inlet and outlet) |
| Minimum Adjustable Integral Time | 0.6 sec. |
The T-5312-1 pneumatic receiver-controller from Johnson Controls serves as a vital component for precise pressure management in pneumatic applications. Weighing 2.63 lbs, this device is constructed primarily from aluminum, providing durability alongside a zinc cover for additional protection. The controller supports surface mounting, simplifying installation in various setups.
Operating within an output signal pressure range of 3 to 15 psig, the T-5312-1 effectively handles a maximum supply and signal pressure of 25 psig, which is crucial for maintaining system integrity. Its broad operating temperature range, from -28.9°C to 65.6°C, makes it suitable for use in fluctuating environmental conditions.
Users can select between direct acting (DA) and reverse acting (RA) control actions based on system requirements. This versatility allows for tailored applications in differing scenarios. Additionally, port connections feature a 1/4-inch barbed fitting for both inlet and outlet, ensuring straightforward integration into existing systems. The minimum adjustable integral time is set at 0.6 seconds, allowing fine-tuning for optimal performance.