The V47AR-1 from Johnson Controls is a temperature-actuated valve specifically designed for regulating water flow based on temperature changes. This model utilizes a direct-acting mechanism allowing it to open as the temperature rises at the sensing bulb, providing robust performance in managing water temperatures.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Johnson Controls |
|---|---|
| Product Type | Temperature-actuated water-regulating valve |
| Product Line | V47 Series |
| Part Number | V47AR-1 |
| Pipe Size/Connection | 1-1/2 in., ASME Flange Connection |
| Body Material | Copper alloy (bronze), contains lead |
| Operating Temperature Range | 24 to 57°C (75 to 135°F opening point range) |
| Valve Action | Direct-acting; opens when temperature increases at bulb |
| Maximum Bulb Temperature | 20°F (11°C) above the operating temperature range |
| Maximum Water Temperature | 77°C (170°F) |
| Max. Supply Water Pressure | 150 psig (1,034 kPa) |
| Capillary Type/Length | Nylon-armored, 6 feet (Style 4) |
| Bulb Size | 11/16 in. diameter x 16-1/4 in. length |
| Standard Bypass Orifice Diameter | 0.093 in. |
The Johnson Controls V47AR-1 valve is constructed to regulate water temperature accurately in various applications. This temperature-actuated water-regulating valve is fitted for pipe sizes measuring 1-1/2 inches and features an ASME flange connection for installation ease. At a weight of 16 lbs, the valve combines solid performance with manageable installation weight.
Built from a copper alloy known as bronze, this valve includes lead and is engineered to withstand operational stress. A key benefit is its direct-acting design, which results in the valve opening as the temperature at the sensing bulb increases. This ensures responsive operation for temperature variations.
The valve efficiently manages a temperature range from 24°C to 57°C, equivalent to a bulb's opening point of 75°F to 135°F. Additionally, the maximum bulb temperature that can be tolerated is 20°F (11°C) above the specified operating range, enhancing its operational flexibility. For water handling, the maximum temperature the valve can accommodate is 77°C (170°F), while it supports a maximum supply water pressure of 150 psig (1,034 kPa).
The capillary component of this model is nylon-armored and 6 feet in length (Style 4), designed for durability and reliability in field settings. The bulb itself measures 11/16 inch in diameter and is 16-1/4 inches long, ensuring effective thermal response. Furthermore, the standard bypass orifice diameter is set at 0.093 inches to facilitate proper flow regulation.