Product image is representative; revision or series may vary. Contact us to request a specific version.
The V47AR-1C from Johnson Controls is a modulating water valve that operates based on temperature changes. This valve is designed to open when the temperature increases, making it ideal for precise thermal regulation in water and glycol systems.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Johnson Controls |
|---|---|
| Product Type | Temperature-Actuated Modulating Water Valve |
| Product Line | V47 Series |
| Part Number | V47AR-1C |
| Valve Action | Opens on Temperature Increase |
| Bulb Style | Style 4, Immersion Style (11/16 in. diameter x 16-1/4 in.) |
| Pipe Size | 1-1/2 in. (ASME Flanged) |
| Opening Point Temperature Range | 24°C to 57°C Cross Ambient |
| Standard Bypass Orifice Diameter | 0.093 in. |
| Maximum Bulb Temperature | 11°C above range |
| Maximum Water Temperature | 77°C |
| Max. Supply Water Pressure | 150 psig (1,034 kPa) |
| Capillary Tubing | 6 ft, Nylon-Armored |
| Seat Repair Kit | STT17A-610R |
| Replacement Sensing Element | SET29A-605R |
| End Connections | ASME Flange |
| Application | Self-operated water/glycol temperature regulation |
The Johnson Controls V47AR-1C is a temperature-actuated modulating water valve that effectively responds to temperature increases by opening. This design enables self-operation within water and glycol systems, allowing for efficient temperature regulation.
It features an immersion style bulb, specifically the Style 4, with a diameter measuring 11/16 inches and a notable length of 16-1/4 inches. The appropriate pipe size for installation is 1-1/2 inches, ensuring compatibility through ASME flanged connections.
Operationally, the valve has an opening point temperature range between 24°C and 57°C cross ambient, while capable of withstanding a maximum bulb temperature of 11°C above the specified range. The maximum temperature for water flowing through the valve is 77°C, and it can tolerate supply pressures of up to 150 psig (1,034 kPa).
For added durability and reliability, the valve includes 6 feet of nylon-armored capillary tubing to protect the sensing element. Users may find the STT17A-610R seat repair kit useful for maintenance, alongside the SET29A-605R replacement sensing element when needed. Overall, the V47AR-1C's robust design ensures effective temperature regulation in various applications.