The FX-16EYT-TBUL is an output module designed by Mitsubishi. It features 16 output points and operates with transistor output types. This module has a maximum resistance load of 0.5 A per point, with the overall load for four resistance points capped at 0.8 A. Induction loads are limited to 12W at 24V DC, ensuring optimal application performance.

Call for an immediate quote
2 Year DO Supply Warranty
Available
Ships from Raleigh, NC
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for FX-16EYT-TBUL

ManufacturerMitsubishi
Product LineFX Series
Part NumberFX-16EYT-TBUL
Weight3.00 lbs (1.36 kg)
Description of ModuleOutput Module
Output Points16 points
Output TypeTransistor
Max. Resistance Load0.5 A/1 point, total load current of 4 resistance load points must be 0.8 A or less
Max. Inductive Load12W, 24V DC
Output Element’s ON Voltage1.5 V
Insulation of CircuitPhotocoupler in base unit
Leakage Current0.1mA 30V DC
Indication of OperationLED is lit when output is active
Response TimeApprox. 0.2 ms or less from OFF to ON, 1.5 ms or less from OFF to ON
Power Consumption2.7 W (112 mA 24 V DC)
Indicator Input Supply24V DC, 7mA/1 point
Switched Voltages5 to 30 V DC
Connection FormTerminal block (M3.5 screws); connect to the PLC with a connector

The Mitsubishi FX-16EYT-TBUL module is a robust output device with 16 dedicated output points. Every output within this transistor module has a maximum resistance load rating of 0.5 A. When utilizing four resistance outputs simultaneously, the total load must remain at or below 0.8 A to ensure compliance with the unit's specifications. Inductive loads are supported up to 12W at 24V DC, optimizing versatility in different applications.

With a minimal ON voltage requirement of 1.5 V, the module ensures a proactive response to signals. The insulation method incorporated into the design utilizes a photocoupler, providing excellent protection for connected circuitry. A leakage current of 0.1mA at 30V DC guarantees further operational integrity.

The FX-16EYT-TBUL features fast response times, registering approximately 0.2 ms or less from OFF to ON and up to 1.5 ms for the reverse state. The module consumes 2.7 W, drawing 112 mA at 24 V DC, making it energy-efficient in operation. Input supply for the indicators operates at 24V DC with a consumption level of 7mA per point, aiding in clear operational feedback.

Users can utilize switched voltages ranging from 5 to 30 V DC. The unit's connection is facilitated through a terminal block, utilizing M3.5 screws for secure attachment. A connector is required for integration with PLC units to create a straightforward installation experience.