The FX2N-16LNK-M is a master block for Mitsubishi's MELSEC-I/O LINK remote I/O system. This device supports a maximum of 128 I/O points across 16 connected units and offers rapid refresh times.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Mitsubishi |
|---|---|
| Product Type | MELSEC-I/O LINK Remote I/O System Master Block |
| Product Line | FX Series |
| Part Number | FX2N-16LNK-M |
| Weight | 0.31 lbs (0.14 kg) |
| Max I/O Points | 128 points (16 units with 4 points each) |
| I/O Refresh Time | Approximately 5.4 ms |
| Communication Speed | 38,400 bps |
| Communication Method | Register Insertion |
| Sync Method | Frame and bit synchronization |
| Error Control | Phase inversion, parity check, and retry on timeout |
| Transmission Path | Bus-type; no terminal resistors are necessary |
| Max Transmission Distance | 200 meters |
| Max Connected Units | 16 stations |
| Error Indication | LED illumination; RUNA and RUNB outputs |
| I/O Point Settings | Configurable to 16, 32, 48, 64, 96, or 128 points |
| External Supply Voltage | 21.6–27.6 V DC |
| Power Consumption (External Supply) | 90 mA at 24 V DC |
| Power Consumption (5 V DC) | 200 mA |
Engineered specifically for remote I/O applications, the Mitsubishi FX2N-16LNK-M serves as a master block in the MELSEC-I/O LINK system. Designed to handle up to 128 total I/O points, this unit can interconnect with 16 devices, each contributing 4 I/O points.
Data refresh is rapid, with a refresh time of about 5.4 ms, ensuring efficient operations. Using the register insertion method, communication occurs at a standard speed of 38,400 bps. Furthermore, this module employs a sync mechanism that utilizes frame and bit synchronization for precise timing.
The FX2N-16LNK-M includes an error control system utilizing phase inversion, parity checks, and retries in the event of a timeout. Its bus-type transmission path eliminates the need for terminal resistors, streamlining installation. The apparatus can transmit data over a distance of up to 200 meters.
It also features an LED for error indication alongside RUNA and RUNB outputs, enabling straightforward system status monitoring. Users can configure I/O points to various totals—16, 32, 48, 64, 96, or 128 points—to match specific requirements.
The external supply voltage for the system ranges from 21.6 to 27.6 V DC, while it consumes 90 mA when powered at 24 V DC. For its 5 V DC supply, consumption is specified at 200 mA, ensuring efficient energy management.