Product image is representative; revision or series may vary. Contact us to request a specific version.
The QS90SR2SN-Q from Mitsubishi is a safety relay extension module designed for integration into Melsec-Q systems. This unit operates on 24 V DC power with a consumption of 35 mA under standard conditions and up to 110 mA when using three extensions.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Mitsubishi |
|---|---|
| Product Line | Melsec-Q |
| Part Number | QS90SR2SN-Q |
| Weight | 3.00 lbs (1.36 kg) |
| Module Type | Safety Relay Extension Unit |
| Module Power Consumption | 35 mA (without extensions), 110 mA (with three extensions) |
| Module Power Voltage | 24 V DC (5% ripple tolerance) |
| Activation Time (Output ON) | Less than or equal to 50 milliseconds |
| Deactivation Time (Output OFF) | Less than or equal to 20 milliseconds |
| Safety Input Channels | 1 safety input (dual-channel) |
| Additional Input Channels | 1 start-up input |
| Safety Input Operating Voltage | 24 V DC (with 5% ripple tolerance) |
| Safety Input Current Rating | 4.6 mA (300 mA during relay activation) |
| Input Electrical Isolation | Relay-based isolation |
| Safety Output Channels | 1 safety output with 3 individual points |
| Load Current Capacity | 3.6 A max per point (Category 4); 5.0 A max per point (Category 3) |
| Minimum Load for Switching | 5 V DC, 5 mA minimum |
| Max Voltage for Output Contacts | 250 V AC or 30 V DC max |
| Operating Temperature Range | 0°C to 55°C |
The Mitsubishi QS90SR2SN-Q is a dedicated safety relay extension unit within the Melsec-Q series, suitable for enhancing system safety. It requires a power input of 24 V DC and can handle a current consumption of 35 mA in its basic configuration. When three extensions are connected, this figure increases to 110 mA.
For signal processing, it features a safety input with dual-channel capability, alongside a start-up input designed for operational initiation. The safety input operates at the same voltage of 24 V DC under specified tolerance levels, consuming 4.6 mA in normal circumstances and up to 300 mA during relay activation, ensuring reliable performance.
This module processes output operations efficiently, achieving activation in a maximum of 50 milliseconds and deactivation in under 20 milliseconds. The QS90SR2SN-Q controls a safety output capable of managing three points, designed to support loads with a maximum capacity of 3.6 A per point under Category 4 conditions or 5.0 A under Category 3 conditions. Moreover, it requires a minimum load of 5 V DC and 5 mA for effective switching.
For voltage handling, the module can manage output contacts with a maximum rating of 250 V AC or 30 V DC, expanding its operational versatility across different applications. The device is designed to function effectively in an environment ranging from 0°C to 55°C, making it a reliable choice for various industrial settings.