Product image is representative; revision or series may vary. Contact us to request a specific version.
The Omron CPM2A-40CDRDNL is a relay output CPU unit built for automation tasks. It features 24 DC input points and 16 corresponding output points for comprehensive control.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Omron |
|---|---|
| Product Line | CPM2 |
| Part Number | CPM2A-40CDRDNL |
| Weight | 3.00 lbs (1.36 kg) |
| CPU Type | Relay Output CPU Unit |
| Input Points | 24, DC input |
| Output Points | 16 |
| Max. Switching Capacity | 2 A at 250 VAC (cosφ = 1), 2 A at 24 VDC (4 A/common) |
| Min. Switching Capacity | 10 mA at 5 VDC |
| Service Life of Relay (Electrical) | 150,000 operations (for 24 VDC resistive load); 100,000 operations (for 240 VAC inductive load, cosφ = 0.4) |
| Service Life of Relay (Mechanical) | 20,000,000 operations |
| ON Delay | 15 ms max. |
| OFF Delay | 15 ms max. |
| Operating Voltage Range | AC: 85 to 264 V, 50/60 Hz; DC: 20.4 to 26.4 V |
| Power Consumption | AC: 60 VA max.; DC: 20 W max. |
| Control Method | Stored program method |
| I/O Control Method | Cyclic scan with direct output |
| Programming Language | Ladder diagram |
| Instruction Length | 1 step per instruction, 1 to 5 words per instruction |
The CPM2A-40CDRDNL from Omron is a relay output CPU unit featuring 24 DC input and 16 output points. With a maximum switching capacity of 2 A at 250 VAC and 2 A at 24 VDC, this unit can handle up to 4 A on a common output. Its minimum switching capability is established at 10 mA and 5 VDC.
Regarding operational endurance, the electrical service life of the relays reaches 150,000 switching cycles under a 24 VDC resistive load. It can withstand 100,000 cycles when dealing with a 240 VAC inductive load at a power factor of 0.4. Mechanically, the relay supports a substantial lifespan of up to 20 million operations, indicating considerable durability.
This product offers ON and OFF delays of up to 15 milliseconds, ensuring timely response in operational processes. The CPM2A-40CDRDNL operates within a voltage range of 85 to 264 VAC at 50/60 Hz or between 20.4 to 26.4 VDC. Power consumption varies, with a maximum of 60 VA for AC and 20 W for DC applications.
Programming this unit uses the ladder diagram methodology, which is prevalent in industrial control systems. Instructions consist of a single step per command and can vary from 1 to 5 words per instruction, providing flexibility in programming complexity.