The Omron CPM2A-40CDRDNL is a relay output CPU unit built for automation tasks. It features 24 DC input points and 16 corresponding output points for comprehensive control.

Call for an immediate quote
2 Year DO Supply Warranty
Available
Ships from Raleigh, NC
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for CPM2A-40CDRDNL

ManufacturerOmron
Product LineCPM2
Part NumberCPM2A-40CDRDNL
Weight3.00 lbs (1.36 kg)
CPU TypeRelay Output CPU Unit
Input Points24, DC input
Output Points16
Max. Switching Capacity2 A at 250 VAC (cosφ = 1), 2 A at 24 VDC (4 A/common)
Min. Switching Capacity10 mA at 5 VDC
Service Life of Relay (Electrical)150,000 operations (for 24 VDC resistive load); 100,000 operations (for 240 VAC inductive load, cosφ = 0.4)
Service Life of Relay (Mechanical)20,000,000 operations
ON Delay15 ms max.
OFF Delay15 ms max.
Operating Voltage RangeAC: 85 to 264 V, 50/60 Hz; DC: 20.4 to 26.4 V
Power ConsumptionAC: 60 VA max.; DC: 20 W max.
Control MethodStored program method
I/O Control MethodCyclic scan with direct output
Programming LanguageLadder diagram
Instruction Length1 step per instruction, 1 to 5 words per instruction

The CPM2A-40CDRDNL from Omron is a relay output CPU unit featuring 24 DC input and 16 output points. With a maximum switching capacity of 2 A at 250 VAC and 2 A at 24 VDC, this unit can handle up to 4 A on a common output. Its minimum switching capability is established at 10 mA and 5 VDC.

Regarding operational endurance, the electrical service life of the relays reaches 150,000 switching cycles under a 24 VDC resistive load. It can withstand 100,000 cycles when dealing with a 240 VAC inductive load at a power factor of 0.4. Mechanically, the relay supports a substantial lifespan of up to 20 million operations, indicating considerable durability.

This product offers ON and OFF delays of up to 15 milliseconds, ensuring timely response in operational processes. The CPM2A-40CDRDNL operates within a voltage range of 85 to 264 VAC at 50/60 Hz or between 20.4 to 26.4 VDC. Power consumption varies, with a maximum of 60 VA for AC and 20 W for DC applications.

Programming this unit uses the ladder diagram methodology, which is prevalent in industrial control systems. Instructions consist of a single step per command and can vary from 1 to 5 words per instruction, providing flexibility in programming complexity.