Technical specifications for CS1W-PTS55

ManufacturerOmron
Product TypeThermocouple input unit
Product LineCS1
Part NumberCS1W-PTS55
Weight10.00 lbs (4.54 kg)
Ambient Operating Temperature0 to 55°C
Number of Inputs8 input channels
Input TypeThermocouple inputs
Current Consumption0.18 Amperes at 5 Volts DC and 0.06 Amperes at 24 Volts DC
Thermocouple TypesB, J, K, L, R, S, and T types
Warm-up TimeApproximately 30 minutes
CompatibilityCS-Series expansion rack or CPU rack
Sensing Method3-wire method
Humidity Tolerance10 to 90% relative humidity or less and in a non-condensing environment
Compliance StandardUL, c-UL, CE, and CSA-certified
Type of External Connection Terminal24-point removable terminal block
Analog/Digital Conversion Speed250 milliseconds per 8 inputs
Mounting MethodBackplane or rack mount

Omron's CS1W-PTS55 is a specialized thermocouple input unit engineered to handle various temperature measurement tasks. Capable of processing eight thermocouple inputs, it supports multiple types, including B, J, K, L, R, S, and T thermocouples. Operating within a temperature range of 0 to 55°C, this unit ensures reliable performance in diverse environmental conditions.

In terms of power requirements, the CS1W-PTS55 consumes 0.18 Amperes at a 5 Volt DC supply and 0.06 Amperes at 24 Volts DC, making it suitable for different system configurations. The warm-up duration required before achieving optimal functionality is approximately 30 minutes.

It utilizes a 3-wire sensing method for accurate measurement. At a weight of just 1 pound (0.45 kilograms), this input unit is designed for efficiency in both functionality and installation. Furthermore, it features humidity tolerance specifications of 10% to 90% relative humidity in non-condensing conditions, supporting various operational settings.

For connection, the unit offers a 24-point removable terminal block, assisting in straightforward installation and maintenance. The analog to digital conversion speed is measured at 250 milliseconds for all eight inputs, ensuring rapid data processing. This thermocouple input unit adheres to stringent compliance standards, including UL, c-UL, CE, and CSA certifications, assuring quality and safety. Finally, it is compatible with either backplane or rack mounting methods, ensuring flexibility in installation.