Free UPS Ground on All Parcel Orders!
+1 (919) 205-4392
Schneider Electric Other 2341-521

Product image is representative; revision or series may vary. Contact us to request a specific version.

2341-521

|

The Schneider Electric 2341-521 is a direct-acting pneumatic receiver-controller, designed to operate effectively under various conditions. This device is integrated with a P541-BASE for easy mounting and offers reliable performance for air pressure regulation.

Call for an immediate quote
2 Year DO Supply Warranty
Available
Ships from Raleigh, NC
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for 2341-521

ManufacturerSchneider Electric
Product TypePneumatic receiver-controller (direct-acting)
Product LineOther
Part Number2341-521
Weight2.13 lbs (0.96 kg)
Mounting ConfigurationPre-mounted on P541-BASE
ConstructionGlass-filled nylon, steel, stainless steel, brass, and neoprene
Min. Operating Temperature2°C
Max. Operating Temperature60°C
Normal Main Air Pressure20-22 PSIG
Maximum Air Pressure30 PSIG
Air Consumption0.021 SCFM max.
Air Flow Capacity8 SCFH
Throttling RangeAdjustable from 2-40% of the primary transmitter span
Authority Adjustment Range10-300%
ConnectionsBarbed nipples, 1/4 in. OD polyethylene or 5/32 in. ID polyurethane tubing

The part number 2341-521 from Schneider Electric is a direct-acting pneumatic receiver-controller, aimed at delivering precise control over air pressure. This unit comes pre-mounted on a P541-BASE, simplifying the installation process. Constructed from a mix of materials such as glass-filled nylon, steel, stainless steel, brass, and neoprene, it provides robust performance throughout its operation.

This controller functions effectively within a temperature range starting from 2°C and extending up to 60°C. It typically operates at main air pressures of 20-22 PSIG and can handle a peak air pressure of 30 PSIG without compromise. Designed for minimal air consumption, it consumes a maximum of 0.021 SCFM while achieving an air flow capacity of 8 SCFH.

Users can benefit from its adjustable throttling range, which allows for modulation between 2% and 40% of the primary transmitter span, accommodating different operational requirements. Additionally, the authority adjustment can be tweaked from 10% to 300%, providing further flexibility.

Connections are streamlined with barbed nipples, which work with either 1/4-inch OD polyethylene or 5/32-inch ID polyurethane tubing, ensuring secure and efficient integration into existing systems.