Free UPS Ground on All Orders!
+1 (919) 205-4392
Schneider Electric Other 56372TD

Product image is representative; revision or series may vary. Contact us to request a specific version.

56372TD

|

The Schneider Electric 56372TD is a time-delay ground-fault relay designed for effective leakage current measurement. It operates with a supply voltage of 110–130 VAC and provides an adjustable sensitivity that can reach up to 30 A, allowing for flexible application in various environments.

Call for an immediate quote
2 Year DO Supply Warranty
Available
Ships from Raleigh, NC
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for 56372TD

ManufacturerSchneider Electric
Product TypeTime-delay ground-fault relay
Product LineOther
Part Number56372TD
UPC785901597094
Weight1.00 lbs (0.45 kg)
MountingDIN-rail
Measured ParameterLeakage current
Supply Voltage110–130 VAC
Fixed Sensitivity Range30 mA–1 A
Adjustable SensitivityUp to 30 A
Timing Range0 s–4.5 s
Time Settings0 s, 60 ms, 150 ms, 250 ms, 310 ms, 500 ms, 800 ms, 1 s, 4.5 s
Maximum System Current3,200 A
OutputsShunt-trip or alarm
Reset MethodManual
Frequency50/60 Hz (up to 400 Hz capable)
Sensor TypeExternal toroidal CT

Part number 56372TD by Schneider Electric serves as a reliable time-delay ground-fault relay. Its operation is supported by a supply voltage between 110 and 130 VAC, making it versatile for various applications. A significant feature is its flexible sensitivity settings, where it can be adjusted up to 30 A while also allowing for a fixed sensitivity range of 30 mA to 1 A.

This relay measures leakage current and is installed on a DIN rail, facilitating straightforward placement within electrical systems. It supports a maximum current rating of 3,200 A, ensuring it can work effectively in high-capacity environments. Users can select from a timing range that spans from 0 seconds to 4.5 seconds, with available preset time settings that include 0 seconds, 60 milliseconds, 150 milliseconds, 250 milliseconds, 310 milliseconds, 500 milliseconds, 800 milliseconds, 1 second, and 4.5 seconds.

Output options include either shunt-trip capabilities or alarm notifications, adding versatility in response methods. This relay also features a manual reset mechanism, ensuring that systems can be easily brought back to operational status following an event. Designed for standard frequencies of 50/60 Hz, it supports operation at frequencies up to 400 Hz, making it adaptable across numerous scenarios. The physical dimensions of the 56372TD relay are 88.9 mm in height, 88.9 mm in width, and 76.2 mm in depth. It utilizes an external toroidal current transformer (CT) as its sensor, ensuring precise measurement of leakage currents.