The HGA36100 from Schneider Electric, a part of the PowerPact series, is engineered as a reliable circuit breaker. It provides a rated current of 100 A and functions with three poles, utilizing a toggle control mechanism. Designed for robust performance, it possesses a maximum breaking capacity of 65 kA and operates efficiently under a rated voltage of 690 VAC.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Schneider Electric |
|---|---|
| Product Type | Circuit Breaker |
| Product Line | PowerPact |
| Part Number | HGA36100 |
| UPC | 785901795056 |
| Weight | 6.00 lbs (2.72 kg) |
| Line Rated Current | 100 A |
| Number of Poles | 3 |
| Control Type | Toggle |
| Breaking Capacity Code | D |
| Maximum Breaking Capacity | 65 kA |
| Rated Operational Voltage | 690 VAC |
| Min. Operating Frequency | 50 Hz |
| Max. Operating Frequency | 60 Hz |
| Rated Impulse Withstand Voltage | 8 kV |
| Trip Unit Technology | Thermal Magnetic |
| Magnetic Tripping Current | 1700 A |
| Magnetic Hold Current | 900 A |
| Mounting Support | Lug |
| Tightening Torque | 44.3 lb.in |
The Schneider Electric HGA36100 circuit breaker is a specialized device designed to ensure safety and control in electrical systems. This unit is rated for a current of 100 A and comprises three poles, making it effective for multi-phase applications. It employs a toggle control type for easy operation.
With a maximum breaking capacity of 65 kiloamperes (kA), this breaker provides a strong protection level against electrical faults. It can effectively handle operational voltages up to 690 VAC. Furthermore, it operates within a frequency range, with a minimum of 50 Hz and a maximum of 60 Hz.
The HGA36100 is built to withstand electrical transients, featuring an impulse withstand voltage rating of 8 kV. The trip unit technology integrates thermal magnetic capabilities, which facilitates reliable and rapid circuit interruption. The magnetic tripping current is rated at 1700 A, and it maintains a hold current at 900 A, ensuring effective overload protection.
For installation convenience, the breaker supports lug mounting, which allows for stable connections in electrical panels or enclosures. It requires a tightening torque of 44.3 lb.in, ensuring secure attachment for optimal performance.