Product image is representative; revision or series may vary. Contact us to request a specific version.
The Schneider Electric HGL26015 circuit breaker is designed for reliable protection in electrical applications. With a line rated current of 15A, it features two poles and employs a toggle control type. This breaker can handle a breaking capacity of 65 kA and is rated for operational use at 690 VAC.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Schneider Electric |
|---|---|
| Product Line | PowerPact |
| Part Number | HGL26015 |
| UPC | 785901433750 |
| Weight | 2.00 lbs (0.91 kg) |
| Product | Circuit Breaker |
| Line Rated Current | 15A |
| Number of Poles | 2 |
| Control Type | Toggle |
| Breaking Capacity | 65 kA |
| Rated Operational Voltage | 690 VAC |
| Network Frequency | 50/60 Hz |
| Rated Impulse Withstand Voltage | 8 kV |
| Trip Unit Technology | Thermal-magnetic |
| Magnetic Tripping Current | 750 A |
| Magnetic Hold Current | 350 A |
| Continuous Current Rating | 80% |
| Rated Insulation Voltage | 750 V |
| Mounting Mode | Unit Mount |
| Tightening Torque | 44.3 lbf.in |
The HGL26015 by Schneider Electric is a robust circuit breaker within the PowerPact series, tailored for effective circuit protection. Rated for 15A, this device includes a dual-pole configuration, facilitating the management of electrical circuits in various applications. The breaker utilizes a toggle-type control mechanism, ensuring straightforward operation.
This unit is capable of handling significant fault conditions with a breaking capacity of 65 kA. It is rated for operation at 690 VAC, allowing it to function effectively in industrial environments. This model operates seamlessly across network frequencies of 50 or 60 Hz, accommodating diverse electrical systems.
The rated impulse withstand voltage is specified at 8 kV, providing added durability against voltage spikes. With thermal-magnetic trip technology, the circuit breaker responds adequately to overloads and short circuits. The magnetic tripping current is calibrated at 750 A, while the magnetic hold current is set at 350 A, ensuring reliable performance under varying load conditions.
Operating at an 80% continuous current rating helps maintain efficiency during regular use. The rated insulation voltage stands at 750 V, supporting safe use within numerous electrical systems. Designed for unit mount installation, the circuit breaker requires a tightening torque of 44.3 lbf.in for secure attachment, ensuring robust installation and operation.