Product image is representative; revision or series may vary. Contact us to request a specific version.
The HJA36090 model from Schneider Electric serves as an electrical circuit breaker with a nominal current rating of 90 amperes. Designed with a triple-pole configuration, it ensures reliable performance in various electrical systems.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Schneider Electric |
|---|---|
| Product Type | Electrical Circuit Breaker |
| Product Line | PowerPact |
| Part Number | HJA36090 |
| UPC | 785901507246 |
| Weight | 6.00 lbs (2.72 kg) |
| Nominal Current Rating | 90 Amperes |
| Pole Configuration | Triple-pole |
| Actuation Method | Manual Toggle Switch |
| Interrupting Capacity (UL 489) | 100 kA at 240V AC, 65 kA at 480V AC, 25 kA at 600V AC, 20 kA at 250V DC |
| Operational Voltage Rating (Ue) | 690V AC per IEC 60947-3 |
| Service Breaking Capacity (Ics) | 100 kA at 220/240V AC, 65 kA at 380/440/415V AC, 25 kA at 500/525V AC, 20 kA at 250V & 500V DC |
| Impulse Withstand Voltage (Uimp) | 8 kV as per IEC 60947-2 |
| Tripping Mechanism | Thermal and Magnetic Trip |
| Instantaneous Trip Setting | 1450 Amperes |
| Continuous Operation Current Factor | 80 percent |
| Insulation Voltage Rating (Ui) | 750V per IEC 60947-2 |
| Mounting Method | I-Line Bracket System |
| Enclosure Protection Level | IP40 (Front-facing Cover) |
| Temperature Tolerance Range | -25°C to 70°C (-13°F to 158°F) |
The Schneider Electric HJA36090 is an electrical circuit breaker tailored for robust circuit protection. As part of the PowerPact series, this model is equipped for nominal currents of 90 Amperes and configured with three poles for effective performance. Operating safely at voltages up to 690V AC as per IEC 60947-3, it is suited for various applications that require reliable disconnection and interruption.
This circuit breaker features an impressive interrupting capacity: it can handle 100 kA at 240V AC, 65 kA at 480V AC, and 25 kA at 600V AC. For DC applications, its interrupting capacity is rated at 20 kA at 250V. The service breaking capacity is equally strong, with ratings of 100 kA at 220/240V AC and 65 kA at 380/440/415V AC, making it versatile for different voltage requirements. Additionally, it has an impulse withstand voltage of 8 kV according to IEC 60947-2, providing added protection against transients.
The tripping mechanism employs both thermal and magnetic principles, allowing for a reliable response to overloads and short circuits. An instantaneous trip setting is offered at 1450 Amperes, and the continuous operation current factor is capped at 80 percent. The insulation voltage rating is positioned at 750V according to IEC 60947-2, further underscoring its efficacy in demanding environments.
Installation is convenient, utilizing an I-Line bracket system, and it is built for an enclosure protection level of IP40, ensuring adequate protection from dust and solid particles on the front face. This circuit breaker operates within a temperature range of -25°C to 70°C (-13°F to 158°F), allowing it to function effectively in a variety of climates.