Product image is representative; revision or series may vary. Contact us to request a specific version.
The JJA36200 from Schneider Electric is a thermal-magnetic circuit breaker featuring a continuous current capability of 160 A and operating across three-phase systems. It supports a rated voltage of 600 V AC and ensures reliability with a short-circuit interrupting capacity of 25 kA, acknowledging UL 489 standards.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Schneider Electric |
|---|---|
| Product Line | PowerPact |
| Part Number | JJA36200 |
| UPC | 785901939245 |
| Weight | 6.00 lbs (2.72 kg) |
| Series | Breakers |
| Device Category | Thermal-Magnetic Distribution Circuit Breaker |
| Continuous Current Rating | 160 A (80% of 200 A rated) |
| Pole Configuration | 3-phase |
| Rated Voltage | 600 V AC, 50/60 Hz |
| Short-Circuit Interrupting Rating | 25 kA at 600 V AC (UL 489) |
| Trip Mechanism | Adjustable thermal-magnetic trip unit |
| Protection Functions | Overcurrent and instantaneous short-circuit protection |
| Mounting Interface | I-Line panel mounting bracket |
| Terminal Conductor Range | 300–350 kcmil aluminum/copper |
| Communication Protocols | Modbus TCP/IP and Ethernet/IP compatibility |
| Ambient Operating Range | -25°C to +70°C (-13°F to +158°F) |
| Front Panel Protection Class | IP40 (dust-protected) |
| Impulse Voltage Resistance | 8 kV per IEC 60947-2 |
| Service Breaking Capacity (Ics) | 65 kA at 240 V AC, 35 kA at 480 V AC (IEC 60947-2) |
The JJA36200 model from Schneider Electric functions as a thermal-magnetic distribution circuit breaker. This unit operates effectively at a continuous current rating of 160 A, which represents 80% of its maximum 200 A rating. Its designed for three-phase applications and is suitable for a voltage rating of 600 V AC, functioning on both 50 Hz and 60 Hz power supplies.
Protection against short-circuits is critical, and this model offers a short-circuit interrupting rating of 25 kA, complying with UL 489 standards. An adjustable thermal-magnetic trip mechanism allows for precise setting to meet specific application requirements. This device provides overcurrent protection alongside instantaneous short-circuit protection to enhance electrical safety and reliability.
Installation is straightforward, as it features a mounting interface that supports I-Line panel brackets. The JJA36200 facilitates terminal connections capable of handling aluminum or copper conductors within a range of 300 to 350 kcmil, ensuring adaptability to various wiring configurations.
Communications for monitoring and control are bolstered with support for Modbus TCP/IP and Ethernet/IP protocols, allowing integration into networked systems. Operating effectively under a temperature range of -25°C to +70°C (-13°F to +158°F), the breaker is reliable for diverse environmental conditions. Additionally, the IP40 front panel rating provides dust protection, and the impulse voltage resistance is rated at 8 kV according to IEC 60947-2.
In terms of breaking capacity, this model handles service interruption effectively, rated for 65 kA at 240 V AC and 35 kA at 480 V AC following IEC 60947-2 standards. Overall, the JJA36200 represents a robust solution for various distribution needs in modern electrical installations.