Product image is representative; revision or series may vary. Contact us to request a specific version.
The Schneider Electric MJL26600 is a molded case circuit breaker (MCCB) designed for robust electrical distribution. This unit supports a line rated current of 600 A and a rated operational voltage of 600 V AC, making it suitable for varying industrial applications.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Schneider Electric |
|---|---|
| Product Type | Molded Case Circuit Breaker (MCCB) |
| Product Line | PowerPact |
| Part Number | MJL26600 |
| UPC | 785901879893 |
| Weight | 28.00 lbs (12.70 kg) |
| Series | Breakers |
| Line Rated Current | 600 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Long-Time Pick-Up Adjustment Range | 300 A to 800 A |
| Number of Poles | 2P |
| Trip Unit Technology | Electronic, Basic (ET 1.0) |
| Utilization Category | Category A |
| Tightening Torque | 442.5 lbf.in (50 N.m) |
| Rated Operational Voltage | 600 V AC, 50/60 Hz |
| Magnetic Tripping Current | 1200 A to 6000 A |
| AWG Gauge Compatibility | 3 x AWG 3/0 to 500 kcmil |
| Rated Service Breaking Capacity (Ics) | 35 kA at 240 V, 25 kA at 415 V |
| Continuous Current Rating | 480 A |
| Mounting Mode | Unit mount with lugs |
| Electrical Connection | Lugs (Load and Line) |
The MJL26600 from Schneider Electric is a molded case circuit breaker, fitting within the MCCB category, intended for comprehensive protection in electrical circuits. This circuit breaker can withstand a rated operational voltage of 600 V AC and operates at frequencies of 50 or 60 Hz. With a line rated current of 600 A, it is adequately equipped to manage substantial loads, ensuring safe and effective circuit management.
Its design includes an adjustable long-time pick-up range of 300 A to 800 A, providing flexibility for adjustments to meet specific current requirements. The continuous current rating sits at 480 A. This unit boasts electronic trip technology (Basic ET 1.0), ensuring accurate response during overload situations. However, it operates with two poles, which is suitable for many applications.
The MJL26600 is rated to endure impulse withstand voltages of up to 8 kV, emphasizing its durability against electrical surges. It can accommodate magnetic tripping currents that range from 1200 A to 6000 A, allowing it to react swiftly in fault conditions. The compatibility with wire gauges from 3 x AWG 3/0 to 500 kcmil enables various electrical connections, ensuring ease of installation.
Installation is straightforward, utilizing a unit mount design with lugs for both load and line connections. The tightening torque requirement is specified at 442.5 lbf.in (50 N.m), which aids in secure mounting and connectivity. Furthermore, the rated service breaking capacity is notable, rated at 35 kA at 240 V and 25 kA at 415 V, making it a reliable choice for protection in demanding environments.