The Schneider Electric QDA221254 circuit breaker provides a rated line current of 125 A and consists of two poles. Designed to operate within a voltage range of 240 V, it features thermal-magnetic trip unit technology, capable of handling magnetic tripping currents up to 2400 A with an adjustable hold current of 1200 A.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Schneider Electric |
|---|---|
| Product Type | Circuit Breaker |
| Product Line | PowerPact |
| Part Number | QDA221254 |
| UPC | 785901619109 |
| Weight | 5.00 lbs (2.27 kg) |
| Line Rated Current | 125 A |
| Number of Poles | 2 |
| Control Type | Operating Handle |
| Breaking Capacity Code | D |
| Breaking Capacity | 25 kA |
| Rated Operational Voltage | 240 V |
| Minimum Operating Frequency | 50 Hz |
| Maximum Operating Frequency | 60 Hz |
| Rated Impulse Withstand Voltage | 8 kV |
| Trip Unit Technology | Thermal-Magnetic |
| Magnetic Tripping Current | 2400 A |
| Magnetic Hold Current | 1200 A |
| Continuous Current Rating | 80% |
| Mounting Mode | I-Line Bracket |
The QDA221254 from Schneider Electric functions as a circuit breaker, essential for providing protection in electrical installations. With a line rated current of 125 A, it can handle various electrical loads efficiently. This device encompasses two poles and is engineered for 240 V rated operational voltage, making it apt for typical applications.
The product is robust, exhibiting a breaking capacity of 25 kA, ensuring it can interrupt high fault currents. The circuit breaker is configured with a thermal-magnetic trip unit, where the magnetic tripping occurs at currents reaching 2400 A, alongside a magnetic hold current of 1200 A, allowing for specific fault conditions. The continuous current rating is managed at 80%, ensuring reliable operation under normal conditions.
For installation, the QDA221254 is compatible with I-Line brackets, facilitating ease of mounting in various applications. It operates effectively within standard frequencies of 50 Hz to 60 Hz. For protection against transient voltages, it has a rated impulse withstand voltage of 8 kV, enhancing its durability in dynamic electrical environments. This circuit breaker reflects a high level of operational integrity, aligning with the needs of modern electrical systems.