The HJL36150AA model from Schneider Electric, within the Square D series, is a molded-case circuit breaker. It operates at a rated current of 150 amperes with three poles configured for 3-phase systems. This device supports a maximum voltage of 690 VAC, making it suitable for a variety of industrial applications.

Call for an immediate quote
2 Year DO Supply Warranty
Available
Ships from Raleigh, NC
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for HJL36150AA

ManufacturerSchneider Electric
Product TypeMolded-Case Circuit Breaker
Product LineSquare D
Part NumberHJL36150AA
GTIN785901839972
Rated Current150 A
Number of Poles3 Poles
Phase Type3 Phase
Rated Voltage690 VAC
Mounting TypeUnit Mounting/Feed-Thru Mounting
Interrupting Rating at 480 Volts AC65 kA
Interrupting Rating at 600 Volts AC25 kA
Interrupting Rating at 240 Volts AC100 kA
Trip Unit TypeThermal-Magnetic
Min. Frequency50 Hz
Max. Frequency60 Hz

The Schneider Electric HJL36150AA, classified as a molded-case circuit breaker, is designed for effective protection in electrical systems. Weighing 4.10 lbs, this circuit breaker can handle a rated current of 150 A across three poles, suitable for 3-phase configurations. With a rated voltage capacity of 690 VAC, it is adaptable for various use cases that require dependable operation.

This breaker allows for two types of mounting: unit mounting and feed-thru mounting, enhancing its versatility for installation in different setups. In terms of its interrupting ratings, the HJL36150AA can withstand 100 kA at 240 Volts AC, 65 kA at 480 Volts AC, and 25 kA at 600 Volts AC, providing robust performance under fault conditions.

To protect your electrical system, it employs a thermal-magnetic trip unit that reacts appropriately to overloads and short circuits. The operational frequency for this device ranges from a minimum of 50 Hz to a maximum of 60 Hz, ensuring reliable performance in standard electrical applications. Overall, the HJL36150AA circuit breaker is a critical component for safeguarding equipment and maintaining system integrity.