Product image is representative; revision or series may vary. Contact us to request a specific version.
Part number GV2ME10 from Schneider Electric is a motor circuit breaker that provides thermal-magnetic protection for motors. This device supports an adjustable thermal protection range from 4 to 6.3 A, with a rated current of 6.3 A.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Schneider Electric |
|---|---|
| Product Type | Motor Circuit Breaker |
| Product Line | TeSys |
| Part Number | GV2ME10 |
| EAN | 3389110343113 |
| Weight | 0.63 lbs (0.28 kg) |
| Magnetic Tripping Current | 91 A |
| Thermal Protection Adjustment Range | 4-6.3 A |
| Rated Current | 6.3 A |
| Control Type | Push-button |
| Breaking Capacity | 100 kA Icu at 230/240 V AC 50/60 Hz; 100 kA Icu at 400/415 V AC 50/60 Hz; 50 kA Icu at 440 V AC 50/60 Hz; 50 kA Icu at 500 V AC 50/60 Hz; 3 kA Icu at 690 V AC 50/60 Hz |
| Motor Power | 2.2 kW at 400/415 V AC 50/60 Hz; 3 kW at 500 V AC 50/60 Hz; 4 kW at 690 V AC 50/60 Hz |
| Network Frequency | 50/60 Hz conforming to IEC 60947-4-1 |
| Utilisation Category | AC-3 conforming to IEC 60947-4-1, Category A conforming to IEC 60947-2 |
| Network Type | AC |
| Poles Description | 3P (3 poles) |
| Trip Unit Technology | Thermal-magnetic |
| Device Application | Motor protection |
The Schneider Electric GV2ME10 is classified as a motor circuit breaker, specifically developed to safeguard motors. Its thermal-magnetic trip unit technology ensures reliable protection. The device runs with a rated current set at 6.3 A and has an adjustable thermal protection range from 4 to 6.3 A.
For magnetic tripping, this model has a significant current value of 91 A. The break capacity varies depending on the voltage level: it stands at 100 kA Icu for both 230/240 V AC and 400/415 V AC, while it reaches 50 kA at both 440 V AC and 500 V AC, with a lower threshold of 3 kA at 690 V AC.
In terms of motor power capabilities, it can handle 2.2 kW at 400/415 V AC, 3 kW at 500 V AC, and up to 4 kW at 690 V AC. This motor circuit breaker operates within a network frequency range of 50/60 Hz according to IEC 60947-4-1 standards, making it suitable for a variety of industrial applications.
Conforming to utilization category AC-3 as per IEC 60947-4-1, the device is compatible with AC network types. This circuit breaker consists of 3 poles (3P), and its control mechanism is via a push-button, facilitating user interaction. The GV2ME10 exemplifies essential features for secure motor protection in various operational environments.