TSXCTY2A

|

The TSXCTY2A component from Schneider Electric is an auxiliary output module designed for TSX Micro PLCs. This unit supports up to two channels with a counting frequency of 40 kHz and operates under the EN/IEC 61131 standards.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for TSXCTY2A

ManufacturerSchneider Electric
Product LineTSX Micro PLCs
Part NumberTSXCTY2A
EAN3389110756975
Weight1.00 lbs (0.45 kg)
Electrical Circuit TypeAuxiliary output conforming to EN/IEC 61131
Response Time< 2.5 ms sensor voltage at loss of 24 V auxiliary input (preset, enable, read)
Channels2
Counting Frequency40 kHz
Power Dissipation4.5 to 6 W
Cycle Time5 ms
Input LogicCurrent sink auxiliary input (preset, enable, read)
Input Compatibility2/3-wire proximity sensors (PNP/NPN), incremental encoder (10-30 V totem pole, 5 V DC RS422)
Input Voltage24 V (18 mA for sensors, 7 mA for auxiliary input, 18 mA for encoder)
Voltage Limits<= 5.5 V for encoder, 19-30 V for sensors and auxiliary input
Voltage State 1>= 11 V for sensors and auxiliary input, >= 2.4 V for encoder
Current State 1>= 3.7 mA for encoder, >= 6 mA for sensors and auxiliary input
Voltage State 0<= 1.2 V for encoder, <= 5 V for sensors and auxiliary input
Current State 0<= 1 mA for encoder, <= 2 mA for sensors and auxiliary input
Output Voltage24 V DC

The Schneider Electric TSXCTY2A is an auxiliary output module intended for use with TSX Micro PLCs. It adheres to the EN/IEC 61131 standards, making it suitable for various industrial applications. This module operates on two channels and can handle a counting frequency of 40 kHz.

When the 24 V auxiliary power is interrupted, the response time is measured at under 2.5 ms, which impacts systems requiring prompt reactions. It features a cycle time of 5 ms, ensuring that it processes tasks efficiently.

The module's input logic functions as a current sink auxiliary input. It is compatible with both 2 and 3-wire proximity sensors, such as PNP/NPN types, as well as incremental encoders running at a voltage of 10-30 V totem pole or 5 V DC RS422.

Operating with a nominal input voltage of 24 V, current requirements include 18 mA for sensors, 7 mA for the auxiliary input, and 18 mA for the encoder. The input voltage limits are set at 19-30 V for sensors and auxiliary inputs, while the encoder operates at a limit of 5.5 V.

For voltage state detection, it establishes a voltage state of 1 at greater than or equal to 11 V for sensors and auxiliary input and a minimum of 2.4 V for the encoder. Current states of 3.7 mA for the encoder, and 6 mA for the sensors and auxiliary inputs, signify active conditions. In contrast, voltage states of zero are recognized at 1.2 V for encoders or 5 V for sensors, with respective current states below 1 mA and 2 mA.

This advanced module also provides an output voltage of 24 V DC to control connected devices effectively.