Product image is representative; revision or series may vary. Contact us to request a specific version.
Siemens' 6SE6400-3TD18-0FD0 is an output filter designed for three-phase applications in the MICROMASTER series. It operates with voltage ratings between 380 and 480 volts AC and accommodates current ratings of 181.6 amps at 40 degrees Celsius, reducing to 145 amps at 50 degrees Celsius.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Siemens |
|---|---|
| Product Type | Output filter (LC filter) |
| Product Line | MICROMASTER |
| Part Number | 6SE6400-3TD18-0FD0 |
| UPC | 662643429466 |
| Weight | 171.00 lbs (77.56 kg) |
| Voltage Rating | 380–480 volts AC |
| Number of phases input | 3-phase |
| Current Rating | 181.6 amps at 40 degrees Celsius / 145 amps at 50°C |
| Frame Size | F |
| Enclosure Type | IP00 / IP20 |
| Mounting | Stand-alone |
| Overvoltage Category | III (VDE 0110) |
| Insulation Class | Class H |
| Maximum Motor Frequency | 150 Hz |
| Motor Overvoltage Limiting | Approximately 1078 volts |
| Maximum Motor Feeder Cable | 200 meters (shielded); 300 m (unshielded) |
| Pulse Frequency | 4 kHz (operation with 2 kHz pulse frequency leads to overheating) |
The 6SE6400-3TD18-0FD0 from Siemens is categorized as an output filter (LC filter) tailored for three-phase systems. The voltage rating ranges from 380 to 480 volts AC. This product operates at a maximum current of 181.6 amps when the ambient temperature is at 40 degrees Celsius, and the rating decreases to 145 amps at 50 degrees Celsius.
Designed in Frame Size F, the device comes in an IP00 / IP20 enclosure type. It is configured for stand-alone mounting, allowing for easy integration into existing systems. The unit meets Overvoltage Category III (VDE 0110) standards and is rated under Insulation Class H, affirming its capability for thermal resistance.
Motor frequency is governed up to a maximum of 150 Hz, providing flexibility in various applications. It also includes a motor overvoltage limitation at approximately 1078 volts. The specifications allow for a maximum shielded motor feeder cable length of 200 meters and up to 300 meters without shielding. }
To ensure reliable operation, it is crucial to maintain a pulse frequency of 4 kHz, as using a 2 kHz pulse frequency can lead to overheating. This output filter is integral for applications requiring precise control and protection in regular operation.