The Siemens 3VA5225-6ED31-0AA0 is a molded case circuit breaker designed for robust performance. It functions effectively with a rated current of 250 amperes across three poles and operates at voltage ratings of up to 600 volts AC or 750 volts DC.

Call for an immediate quote
2 Year DO Supply Warranty
Available
Ships from Raleigh, NC
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for 3VA5225-6ED31-0AA0

ManufacturerSiemens
Product TypeMolded Case Circuit Breaker
Product LineSENTRON
Part Number3VA5225-6ED31-0AA0
UPC804766308147
Rated Current250 Amperes
Poles3 Poles
Voltage Rating600 Volts AC, 750 Volts DC
Trip UnitTM210
Interrupt Rating100 kA at 240 Volts AC, 65 kA at 480 Volts AC, 25 kA at 600 Volts AC
Connection TypeFeed-Thru
Operational Short Circuit SettingFixed ~ 2500 Amperes
Trip FunctionLong Time + Instantaneous
EnclosureIP 40 on Front
CertificationUL 489, IEC, RoHS
Operating Temperature-25 to 60 degrees Celsius

The Siemens SENTRON series introduces the 3VA5225-6ED31-0AA0 molded case circuit breaker, engineered for reliability in electrical distribution systems. This breaker is rated for a current of 250 amperes and operates with three poles to enhance its functionality. Rated for voltages of up to 600 volts AC and 750 volts DC, it is suitable for various applications.

In terms of protective features, the trip unit is designated TM210 and provides an interrupt capability of 100 kA at 240 volts AC. Further interrupt ratings include 65 kA at 480 volts AC and 25 kA at 600 volts AC. An integral fixed short circuit setting of around 2500 amperes supports operational safety against overloads.

The trip function includes both long time and instantaneous responses, making this breaker adaptable to different conditions. With a feed-thru connection type, installation is simplified within electrical panels. The unit is designed with an IP 40 enclosure on the front, shielding it against dust and contact with solid foreign objects. Certification compliance includes UL 489, IEC, and RoHS, ensuring that it meets international safety and environmental standards. Operating temperature limits are between -25 to 60 degrees Celsius.