The 6SL3000-0CE41-5AA0 from Siemens is a line reactor designed for industrial use in the SINAMICS S120 series. It can operate effectively with a nominal voltage between 380 and 480 volts AC, supporting an impressive current rating of 1458 amps.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Siemens |
|---|---|
| Product Type | Line Reactor |
| Product Line | SINAMICS S120 |
| Part Number | 6SL3000-0CE41-5AA0 |
| UPC | 662643432145 |
| Weight | 121.00 lbs (54.88 kg) |
| Nominal Voltage | 380–480 volts AC |
| Nominal Current | 1458 amps |
| Frequency Range | 47–63 Hz |
| Mounting | Panel or floor-mounted; adequate cooling space required |
| Cooling | Natural convection |
| Cable Separation | 200 mm between power and control wiring |
| Conductor Type | Copper; UL compliance |
| Surface Temperature | May exceed 80 °C during operation |
| Environment | Industrial indoor, ventilated area |
| Compliance | RoHS |
| Operating Temperature | 0 to 40 degrees Celsius |
The model 6SL3000-0CE41-5AA0 by Siemens represents a robust line reactor optimized for industrial environments. This unit is designed to handle voltages ranging from 380 to 480 volts AC, with a maximum nominal current capability of 1458 amps. Its operating frequency spans 47 to 63 hertz, ensuring compatibility across various operational settings.
Installation options include panel or floor-mounting. However, it is crucial to ensure adequate cooling space is available since this unit relies on natural convection for heat dissipation. During operation, the surface temperature can exceed 80 °C, highlighting the need for careful environmental considerations. The reactor is intended for use in ventilated indoor industrial areas and meets RoHS compliance regulations.
For wiring configurations, the reactor mandates a minimum cable separation of 200 mm between power and control lines to reduce potential interference and maintain effective performance. The conductors are made of copper and comply with UL standards, showcasing a commitment to quality and safety. Operating temperatures for this device should fall between 0 and 40 degrees Celsius, making it suitable for a range of working conditions.