| Manufacturer | Siemens |
|---|---|
| Product Type | 3RT14 Series Power Contactor |
| Product Line | SIRIUS |
| Part Number | 3RT1466-6AP36 |
| UPC | 754554773452 |
| Weight | 2.75 lbs (1.25 kg) |
| Series | Contactors |
| AC-1 Operational Current Capacity | 400 A (690 V, 40°C); 380 A (690 V, 55-60°C) |
| Main Circuit Voltage Rating | 690 V AC, 3-pole |
| Control Circuit Voltage Range | 220–240 V AC/DC (50-60 Hz), with 0.8–1.1 operating range factor |
| Auxiliary Contact Configuration | 2 Normally Open (NO) + 2 Normally Closed (NC) |
| Power Dissipation at Rated Load | 105.6 W (total), 35.2 W per pole |
| Mechanical Durability | 10 million switching cycles (standard) |
| Surge Voltage Withstand | 8 kV (main circuit), 6 kV (auxiliary circuit) |
| Operating Temperature Range | -25°C to +60°C (ambient) |
| Main Circuit Connection | Busbar (25 mm width, 6 mm thickness) for 70–240 mm² conductors |
| Short-Circuit Protection Requirements | gG fuses (500 A, 690 V, 100 kA) for main circuit coordination |
| Insulation Voltage Rating | 1000 V (main circuit), 500 V (control/auxiliary circuit) |
| Switching Frequency (AC-1) | Up to 600 operations/hour |
| Environmental Protection Rating | IP00 (front); IP20 with terminal cover |
The 3RT1466-6AP36 from Siemens is a robust power contactor designed for effective operation in industrial environments. It can manage an AC-1 operational current capacity of 400 A at a temperature of 40°C and can sustain 380 A when the temperature rises to 55°C or 60°C. Significantly, this contactor supports a main circuit voltage of 690 V AC and includes three poles.
The control circuit functions efficiently within a voltage range of 220–240 V AC/DC at 50-60 Hz, able to utilize an operating range factor of 0.8 to 1.1. Two normally open and two normally closed auxiliary contacts allow for versatile integration into various control systems. Power dissipation at a rated load totals 105.6 W, with each pole dissipating approximately 35.2 W.
This contactor has been engineered for extensive mechanical durability, rated for approximately 10 million switching cycles under standard conditions. For instances of electrical surges, it can withstand a peak surge voltage of 8 kV on the main circuit and 6 kV on the auxiliary. It is designed to function within an ambient temperature range from -25°C to +60°C.
For connectivity, the main circuit connection utilizes a busbar designed to accommodate conductors with dimensions ranging from 70 mm² to 240 mm², supported by a busbar of 25 mm width and 6 mm thickness. Adhering to safety standards, short-circuit protection requires gG fuses rated at 500 A, 690 V for effective coordination.
Insulation voltage ratings stand at 1000 V for the main circuit and 500 V for the control and auxiliary circuits. Capable of achieving a switching frequency of up to 600 operations per hour, this contactor adheres to environmental protection classifications of IP00 at the front and IP20 when equipped with a terminal cover, emphasizing its suitability for various applications.