| Manufacturer | Siemens |
|---|---|
| Product Line | SIRIUS |
| Part Number | 3RW4446-6BC44 |
| UPC | 754554924021 |
| Weight | 11.56 lbs (5.24 kg) |
| Module Type | Soft starter |
| Operational Current | 356A (40°C), 315A (50°C), 280A (60°C) |
| Operational Current for 3-Phase Motors at Inside-Delta Circuit | 617A (40°C), 546A (50°C), 485A (60°C) |
| Yielded Mechanical Performance for 3-Phase Motor (230V) | 110000W (standard circuit), 200000W (inside-delta circuit) |
| Yielded Mechanical Performance for 3-Phase Motor (400V) | 200000W (standard circuit), 355000W (inside-delta circuit) |
| Operational Frequency | 50 to 60 Hz |
| Operating Voltage at Standard Circuit | 200 to 460V |
| Operating Voltage at Inside-Delta Circuit | 200 to 460V |
| Minimum Load | 8% |
| Overload Protection Rated Current | 71A |
| Power Loss at 40°C | 174W |
| Control Supply Voltage | 230V at 50Hz and 60Hz |
| Control Supply Voltage Type | AC |
| Insulation Voltage | 690V |
| Operational Temperature | 60°C |
Designed for reliable control, the Siemens 3RW4446-6BC44 is a soft starter that enables smooth operation of three-phase motors. This unit provides various operational currents, rated at up to 356A at 40°C, reducing to 280A at higher temperatures (60°C). For an inside-delta circuit, it manages robust currents of 617A (at 40°C) and 485A (at 60°C).
The soft starter can deliver impressive mechanical performance levels, providing functionalities of up to 110,000W for a standard circuit at 230V. For inside-delta applications, this performance reaches 200,000W. At 400V, the soft starter delivers mechanical power outputs of 200,000W in standard configurations and 355,000W in inside-delta configurations.
This device operates within an input frequency range of 50 to 60 Hz and can accommodate operating voltages between 200 and 460 Volts. It features a minimum load requirement of 8%, ensuring suitable operation characteristics.
Safety mechanisms are in place, including overload protection rated at 71A. The soft starter experiences a power loss of 174W when in a thermal state of 40°C. Furthermore, the control supply voltage is set at 230V and functions reliably under both AC and standard operational conditions.
With an insulation voltage capacity of 690V, the soft starter can safely operate up to a temperature of 60°C, making it a robust choice for various industrial applications.