Product image is representative; revision or series may vary. Contact us to request a specific version.
The Siemens 547-311B is a pressure monitor used to track room conditions accurately. With a pressure scale of ±0.5 in WC (12.5 Pa), it is suitable for maintaining desired environmental parameters in various settings.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Siemens |
|---|---|
| Product Type | Room condition/pressure monitor |
| Product Line | SRCM Room Condition Monitors |
| Part Number | 547-311B |
| Pressure Range (Full Scale) | 0.5 (-/+) in WC (12.5 Pa) |
| Accuracy (Full Scale, RSS) | 0.5%, -/+ |
| Excitation Voltage Rating (AC) | 18 to 32 Volts AC |
| Input Voltage Frequency | 50 to 60 Hz |
| Operating Temperature Range | 0 to 50°C (electronics only) |
| Storage Temperature Range | -30°C to 70°C |
| Humidity Range | 5 to 95% RH (Non-Condensing) |
| Power Consumption | 10 W max., 3 W typical |
| Output Signal (Voltage) | 0 to 5 Volts DC or 0 to 10 Volts DC |
| Output Signal (Current) | 4 to 20 mA |
| Display | 4.3 in. dimmable TFT LCD, 480 x 272 |
| Case Material | Fire-retardant plastic, UL94 V-0 |
| Electrical Connection | Removable terminal block |
The Siemens 547-311B is a sophisticated room condition and pressure monitoring device designed for precision in various environments. The monitor calculates pressure with a full-scale range of ±0.5 in WC, equivalent to 12.5 Pa. Its weight is a manageable 1.22 lbs, making installation straightforward.
Operating with an accuracy of ±0.5% RSS, the unit ensures reliable measurements for effective environmental control. It requires an AC excitation voltage between 18 to 32 Volts to function, with a frequency input range of 50 to 60 Hz.
For temperature operations, the monitor can handle an ambient range from 0 to 50 °C, while storage capabilities extend from -30 °C to 70 °C, ensuring adaptability for different situations. It also withstands humidity levels from 5% to 95% relative humidity in non-condensing conditions, further adding to its reliability.
Power consumption is efficient, with a maximum of 10 W and a typical usage of around 3 W. Output signals can be configured for voltage (0 to 5 Volts DC or 0 to 10 Volts DC) or current (4 to 20 mA), giving users flexibility in connectivity and integration.
The display, a 4.3-inch dimmable TFT LCD with a resolution of 480 x 272, provides clear visibility of monitored conditions, while the enclosure is crafted from UL94 V-0 rated fire-retardant plastic, enhancing safety. The electrical connection is made via a removable terminal block, allowing for easy maintenance or reconfiguration.